Quickstart

This is a secure On/Off Power Switch for XXXQFrequencyName. To run this device please connect it to your mains power supply. 1) Plug the device into a socket nearby the main Z-Wave controller. 2) The LED ring will glow red signalling not being added (remove the device otherwise). 3) Set the main Z-Wave controller into adding mode (see the controller’s manual). 4) Quickly, triple click the B-button located on the casing. 5) Wait for the adding process to end. 6) Successful adding will be confirmed by the Z-Wave controller.



Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law. The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material. Use this equipment only for its intended purpose. Follow the disposal instructions. Do not dispose of electronic equipment or batteries in a fire or near open heat sources.

Product Description

FIBARO Wall Plug is a universal, Z-Wave Plus compatible, remotely controlled outlet adapter. This device may be applied wherever you want to control electrical devices with up to 2500W load. The Wall Plug is equipped with a power and energy metering function. It uses a LED ring to visualize the current load with colour changing illumination and operating mode. This is the smallest and most attractive device of this type available in the world. The Wall Plug may be operated using the B-button located on its casing or via any Z-Wave compatible controller.

Main features:
• Compatible with any Z-Wave or Z-Wave Plus Controller.
• Supports protected mode (Z-Wave network security mode) with AES-128 encryption.
• Extremely easy installation - simply plug the device into the mains socket.
• Works as a Z-Wave signal repeater.
• Active power and energy consumption metering.
• Current value of the load and operating mode are indicated by the multi-colour LED ring.

Reset to factory default Resetting the device is not the recommended way of removing the device from the Z-Wave network. Use reset procedure only if the primary controller is missing or inoperable. Certain device removal can be achieved by the procedure of removing described in “Adding/ removing the device”on page 6. 1) Make sure the device is powered. 2) Press and hold the B-button. 3) Wait for the LED ring to glow yellow (4th menu position). 4) Release the B-button. 5) Click the B-button once to confirm selection. 6) After few seconds the device will restart with factory settings, which is signalled with the red ring colour.
Inclusion 1) Plug the device into a socket nearby the main Z-Wave controller. 2) The LED ring will glow red signalling not being added (remove the device otherwise). 3) Set the main Z-Wave controller into adding mode (see the controller’s manual). 4) Quickly, triple click the B-button located on the casing. 5) Wait for the adding process to end. 6) Successful adding will be confirmed by the Z-Wave controller.
Exclusion 1) Plug the device into a socket nearby the main Z-Wave controller. 2) The LED ring will glow green signalling being added (removing is not necessary otherwise). 3) Set the main Z-Wave controller into remove mode (see the controller’s manual). 4) Quickly, triple click the B-button located on the casing. 5) Wait for the removing process to end. 6) Successful removing will be confirmed by the Z-Wave controller.
NIF XXXNIF
Wakeup Wakeup Description FIBARO Wall Plug is powered with mains voltage so it is always awake.
Protection XXXProtection
FirmwareUpdate XXXFirmwareUpdate
SetAssociation XXXSetAssociation

Association Groups:

Group Number Maximum Nodes Description
1 1 u201cLifelineu201d reports the device status and allows for assigning single device only (main controller by default).
2 10 u201cOn/Off (button)u201d devices in this group will be switched on or off when relay status is changed using the B-button (done via BASIC SET command frames).
3 10 u201cOn/Off (power)u201d devices in this group will be switched on or off depending on the current load (done via BASIC SET command frames).

Configuration Parameters

Parameter 1: Always On function

Once activated, Wall Plug will keep the connected device constantly ON, will stop reacting to alarm frames or pushing the B-button. u201cAlways Onu201d function turns the Wall Plug into a power and energy meter. Connected device will not be turned off upon receiving an alarm frame from another Z-Wave device (parameter 31 will be ignored). In u201cAlways onu201d mode, connected device may be turned off only after user defined power has been exceeded (parameter 3). In such a case, connected device can be turned on again by pushing the B-button or sending a control frame. By default, overload protection is inactive.
Size: 1 Byte, Default Value: 0

Setting Description
0 function inactive
1 function activated

Parameter 10: High priority power report

This parameter determines the minimum percentage change in active power that will result in sending power report to the main controller with the highest priority in the Z-Wave network. By default, the Wall Plug immediately sends the power report if the power load changes by 80%. NOTE In extreme cases, reports may be sent every second if rapid and significant power load changes occur. Frequent reporting may overload the Z-Wave network so these parameteru2019s settings should reflect significant changes in power load only.
Size: 1 Byte, Default Value: 80

Setting Description
1 - 99 power change in percent
100 reports are disabled

Parameter 11: Standard power report

This parameter determines the minimum percentage change in active power that will result in sending power report to the main controller Compared to parameter 10, the maximum number of reports sent is reduced (parameter 12) to 5 in a specified time interval. In addition, the frames are not sent in EXPLORE mode, which prevents overloading the Z-Wave network. By default changes in power load may be reported up to 5 times per 30 seconds, when power load changes by 15%.
Size: 1 Byte, Default Value: 15

Setting Description
1 - 99 power change in percent
100 reports are disabled

Parameter 12: Power reporting interval

This parameter defines how frequently standard power reports (parameter 11) are sent. By default the Wall Plug sends up to 5 reports each 30 seconds, provided the power load changes by 15%.
Size: 2 Byte, Default Value: 30

Setting Description
5 - 600 in seconds

Parameter 13: Energy reporting threshold

This parameter specifies the minimum change in energy consumption (in relation to the previously reported), that will result in sending a new report.
Size: 2 Byte, Default Value: 10

Setting Description
0 energy reports inactive
1 - 500 (0.01-5kWh, step 0.01kWh) - threshold

Parameter 14: Power and energy periodic reports

This parameter defines time period between reports sent when changes in power load have not been recorded or if changes are insignificant (not exceeding values of parameters 20, 21 and 23). By default reports are sent every hour.
Size: 2 Byte, Default Value: 3600

Setting Description
0 periodic reports inactive
5 - 32400 in seconds

Parameter 15: Measuring energy consumed by the Wall Plug itself

This parameter determines whether energy metering should include the amount of energy consumed by the Wall Plug itself. Results are being added to energy consumed by controlled device.
Size: 1 Byte, Default Value: 0

Setting Description
0 function inactive
1 function activated

Parameter 2: Remember device status after a power failure

This parameter determines how the Wall Plug will react in the event of power supply failure (e.g. taking out from the electrical outlet). After the power supply is back on, the Wall Plug can be restored to previous state or remain switched off. This parameter is ignored in u201eAlways Onu201d mode - the device automatically turns ON after plugging it into the socket.
Size: 1 Byte, Default Value: 1

Setting Description
0 device remains switched off
1 device restores the state from before the power failure

Parameter 20: Control of u201eOn/Off (Button)u201d association group (2) devices

Controlling devices with the B-Button. This parameter is inactive in u201cAlways Onu201d mode (parameter 1). Control as the Wall Plug: u2022 switching the Wall Plug on - switch the devices on (parameter 24) u2022 switching the Wall Plug off - switch the devices off (parameter 24) Control opposite to the Wall Plug: u2022 switching the Wall Plug on - switch the devices off u2022 switching the Wall Plug off - switch the devices on
Size: 1 Byte, Default Value: 0

Setting Description
0 control as the Wall Plug
1 control opposite to the Wall Plug

Parameter 21: DOWN value - u201eOn/Off (Power)u201d association group (3)

Lower power threshold, used in parameter 23. DOWN value cannot be higher than a value specified in parameter 22.
Size: 2 Byte, Default Value: 300

Setting Description
0 - 24900 (0.0-2490.0W, step 0.1W)

Parameter 22: UP value - u201eOn/Off (Power)u201d association group (3)

Upper power threshold, used in parameter 23. UP value cannot be lower than a value specified in parameter 21.
Size: 2 Byte, Default Value: 500

Setting Description
100 - 25000 10.0-2500.0W, step 0.1W)

Parameter 23: The response after exceeding defined power values

This parameter defines the way that 3rd association group devices are controlled. Depends on the actual measured power (as parameters 21 and 22 settings).
Size: 1 Byte, Default Value: 6

Setting Description
1 turn the associated devices ON, once the power drops below DOWN value (parameter 21)
2 turn the associated devices OFF, once the power drops below DOWN value (parameter 21)
3 turn the associated devices ON, once the power rises above UP value (parameter 22)
4 turn the associated devices OFF, once the power rises above UP value (parameter 22)
5 combination of 1 and 4. Turn the associated devices ON, once the power drops below DOWN value (parameter 21). Turn the associated devices OFF, once the power rises above UP value (parameter 22).
6 combination of 2 and 3. Turn the associated devices OFF, once the power drops below DOWN value (parameter 21). Turn the associated devices ON, once the power rises above UP value (parameter 22).

Parameter 24: SWITCH ON value - u201eOn/Offu201d association groups

The value of BASIC SET command frame sent to the devices associated in u201eOn/Offu201d association groups (2, 3). u201eOn/Off (Button)u201d association group - in accordance with parameter 20. u201eOn/Off (Power)u201d association group - in accordance with parameter 23. NOTE Setting parameter 24 to appropriate value will result in: 0 - turning off associated devices 1-99 - forcing level of associated devices 255 - setting associated devices to the last remembered state or turning them on
Size: 2 Byte, Default Value: 255

Setting Description

Parameter 3: Overload safety switch

This function allows to turn off the controlled device in case of exceeding the defined power. Controlled device will be turned off even if u201cAlways Onu201d function is active (parameter 1). Controlled device can be turned back on via B-button or sending a control frame. By default this function is inactive. This functionality is not an overload safety protection nor a short circuit protection. Circuit needs additional short circuit and overload protection. CAUTION The device has a protection that will turn the load off in the case of detecting current greater than 110% of rated current. It is a safety function and it cannot be turned off. After its activation the load can be turned on back again by pressing the B-button or sending a control frame. This function is independent of overload safety switch set in the parameter no. 3.
Size: 2 Byte, Default Value: 0

Setting Description
0 function inactive
10 - 30000 (1.0-3000.0W, step 0.1W) - power threshold

Parameter 30: Active alarms

Define Z-Wave network alarms to which the Wall Plug will respond.
Size: 1 Byte, Default Value: 63

Setting Description
1 general alarm
2 smoke alarm
4 CO alarm
8 CO2 alarm
16 high temperature alarm
32 flood alarm

Parameter 31: Response to alarm frames

This parameter defines how the Wall Plug will respond to alarms (deviceu2019s status change). In case of values 1 or 2 the Wall Plug is operating normally and LED ring signals an alarm through time defined in parameter 32 or until the alarm is cancelled. In case of values 5 to 50 the Wall Plug does not report status change, power changes, ignores BASIC SET command frames. After time defined in parameter 32 or after the alarm cancellation, connected device is set to the previous state. NOTE If u201cAlways Onu201d function is active (parameter 1), settings of parameter 31 are ignored.
Size: 1 Byte, Default Value: 0

Setting Description
0 no reaction
1 turn connected device on
2 turn connected device off
5 - 50 (0.5-50.0s, step 0.1s) - cyclically change device state with set period

Parameter 32: Alarm state duration

This parameter specifies the duration of alarm state. If a device sending an alarm frame through the Z-Wave network sets alarm duration as well, this settings are ignored.
Size: 2 Byte, Default Value: 600

Setting Description
1 - 32400 in seconds

Parameter 40: Power load for violet colour

This parameter determines active power value, which when exceeded, causes the LED ring flash violet. Function is active only when parameter 41 is set to 0 or 1.
Size: 2 Byte, Default Value: 25000

Setting Description
1000 - 30000 100.0-3000.0W, step 0.1W

Parameter 41: LED ring colour when controlled device is on

When set to 1 or 2, LED ring colour will change depending on active power and parameter 40. Other colours are set permanently and do not depend on power consumption.
Size: 1 Byte, Default Value: 1

Setting Description
0 illumination turned off completely
1 colour changes continuously depending on active power
2 colour changes in steps depending on active power
3 white
4 red
5 green
6 blue
7 yellow
8 cyan
9 magenta

Parameter 42: LED ring illumination colour when controlled device is off


Size: 1 Byte, Default Value: 0

Setting Description
0 illumination turned off completely
1 LED ring is illuminated with a colour corresponding to the last measured power, before the controlled device was turned off
3 white
4 red
5 green
6 blue
7 yellow
8 cyan
9 magenta

Parameter 43: LED ring illumination colour at the Z-Wave network alarm detection


Size: 1 Byte, Default Value: 0

Setting Description
0 illumination turned off completely
1 no change in colour. LED ring colour is determined by settings of parameters 41 or 42
2 LED ring flashes red/blue/white
3 white
4 red
5 green
6 blue
7 yellow
8 cyan
9 magenta

Parameter 50: Associations in Z-Wave network security mode

This parameter defines how commands are sent in specified association groups: as secure or non-secure. Parameter is active only in Z-Wave network security mode. This parameter does not apply to 1st u201eLifelineu201d group.
Size: 1 Byte, Default Value: 3

Setting Description
0 none of the groups sent as secure
1 2nd group sent as secure
2 3rd group sent as secure
3 2nd and 3rd group sent as secure

Technical Data

Hardware Platform ZM5202
Device Type On/Off Power Switch
Network Operation Always On Slave
Firmware Version HW: 2 FW: 3.15:03.02
Z-Wave Version 6.51.06
Certification ID ZC10-16035016
Z-Wave Product Id 0x010F.0x0602.0x1001
Frequency Europe - 868,4 Mhz
Maximum transmission power 5 mW
EuropeOn/Off Power Switch