Inclusion: Including the RTH100Z into an Existing Network:1. Set your primary controller to Include mode, to add the RTH100Z as a node on your network (see your controllers user manual for detailed instructions).2. Press and release the Install button. The controller will indicate the device has been included into the network.Your controller will indicate the RTH100Z was successfully added to its network (see your controllers user manual for details).Inclusion and exclusion are always done at normal transmit power mode.If your controller supports NWI, then you can optionally set the primary to NWI include mode. Please note that NWI inclusion mode does not end when you have included a new node.This allows multiple nodes to be included without having to physically go back to the controller to initiate the next inclusion.Therefore you must manually terminate NWI inclusion mode at the controller when you have finished including any new nodes to the network.Since intermediate included nodes will assist the inclusion process by routing messages, we recommend that nodes close to the primary controller be installed first, proceeding out in consecutive rings from the controller.Note: Consult your controllers user manual for details on removing a device from a Z-Wave network.
Remote Temperature and Humidity Sensor for HVAC market
Reset to factory default | Factory Reset To reset the RTH100Zs configurations and Z-Wave parameters to Factory Settings (Including association groups and scene configurations), and remove the RTH100Z from any Z-Wave network: Note: Please use this procedure only when the network primary controller is missing or otherwise inoperable1. Hold down the Install button for approximately 10 seconds 2. Release the install button (the RTH100Z will reset all internal configuration including z-wave configurations). The unit will then reset. 3. When the Status LED begins to blink (un-enrolled) the unit has finished restoring configurations is running in normal mode. |
Inclusion | Inclusion: Including the RTH100Z into an Existing Network:1. Set your primary controller to Include mode, to add the RTH100Z as a node on your network (see your controllers user manual for detailed instructions).2. Press and release the Install button. The controller will indicate the device has been included into the network.Your controller will indicate the RTH100Z was successfully added to its network (see your controllers user manual for details).Inclusion and exclusion are always done at normal transmit power mode.If your controller supports NWI, then you can optionally set the primary to NWI include mode. Please note that NWI inclusion mode does not end when you have included a new node.This allows multiple nodes to be included without having to physically go back to the controller to initiate the next inclusion.Therefore you must manually terminate NWI inclusion mode at the controller when you have finished including any new nodes to the network.Since intermediate included nodes will assist the inclusion process by routing messages, we recommend that nodes close to the primary controller be installed first, proceeding out in consecutive rings from the controller.Note: Consult your controllers user manual for details on removing a device from a Z-Wave network. |
Exclusion | Exclusion: Removing the RTH100Z from a Network:1. Set your primary controller to Remove mode, to remove the RTH100Z as a node on your network (see your controllers user manual for detailed instructions).2. Press and release the Install button. The controller will indicate the device has been removed from the network.3. The device will automatically be restored to its default settings |
NIF | XXXNIF |
Wakeup | To wake-up the device for configuration you can triple-press the install button. |
Protection | XXXProtection |
FirmwareUpdate | XXXFirmwareUpdate |
SetAssociation | XXXSetAssociation |
Group Number | Maximum Nodes | Description |
---|---|---|
1 | 1 | Z-Wave Plus Lifeline |
2 | 5 | Temperature Reports |
3 | 5 | Humidity Reports |
4 | 5 | Temperature driven BASIC_SETs |
5 | 5 | Humidity driven BASIC_SETs |
6 | 5 | Battery Reports |
Time between sending Battery Reports in Hours Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
1 - 127 | 1127 hours |
0 | Disabled |
Group2 Temperature Delta Autosend Threshold (how many degree change from the last autosend) Size: 1 Byte, Default Value: 10
Setting | Description |
---|---|
1 - 50 | In tenths of degrees |
0 | Disabled |
Group2 Periodic Temperature Send Interval (minutes) Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
1 - 120 | Minutes |
0 | Disabled |
Send Basic Set On above humidity See also Register 20 Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 - 100 | Percent |
0 | Disabled |
Send Basic Set On below humidity See also Register 20 Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 - 100 | Percent |
0 | Disabled |
Send Basic Set Off above humidity See also Register 20 Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 - 100 | Percent |
0 | Disabled |
Send Basic Set Off below humidity See also Register 20 Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 - 100 | Percent |
0 | Disabled |
Group1- Humidity Delta Autosend Threshold (how many degree change from the last autosend) Size: 1 Byte, Default Value: 5
Setting | Description |
---|---|
1 - 50 | Percent |
Group1- Periodic Humidity Send Interval Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
1 - 120 | Minutes |
0 | Disabled |
Group3- Humidity Delta Autosend Threshold (how many degree change from the last autosend) Size: 1 Byte, Default Value: 5
Setting | Description |
---|---|
1 - 30 | Percent |
0 | Disabled |
Group3- Periodic Humidity Send Interval (minutes) Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
1 - 120 | Minutes |
0 | Disabled |
Send Basic Set On above temp See also Register 20 Size: 1 Byte, Default Value: 121
Setting | Description |
---|---|
15 - 120 | 15120 Degrees F |
121 | Disabled |
Basic Set Options for Temp and Humidity Size: 1 Byte, Default Value: 1
Setting | Description |
---|---|
2 | Enable Configuration Registers 2, 5, 13, 14 |
1 | Enable Configuration Registers 2, 5, 12, 15 |
3 | Enable Configuration Registers 3, 4, 12, 15 |
4 | Enable Configuration Registers 3, 4, 13, 14 |
Temp offset Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
249 - 7 | Degrees(-7 to 7) |
Humidity offset Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
249 - 7 | Percent(-7 to 7) |
Humidity Filter Time Constant Size: 1 Byte, Default Value: 30
Setting | Description |
---|---|
1 - 60 | Minutes |
Send Basic Set On above temp See also Register 20 Size: 1 Byte, Default Value: 121
Setting | Description |
---|---|
15 - 120 | 15120 Degrees F |
121 | Disabled |
Send Basic Set On below temp See also Register 20 Size: 1 Byte, Default Value: 121
Setting | Description |
---|---|
15 - 120 | 15120 Degrees F |
121 | Disabled |
Send Basic Set Off below temp See also Register 20 Size: 1 Byte, Default Value: 121
Setting | Description |
---|---|
15 - 120 | 15120 Degrees F |
121 | Disabled |
Make multiple attempts for all Basic Set Commands Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
1 - 5 | Number of extra attempts sent every minute after first send |
0 | Disabled |
Temp Units Size: 1 Byte, Default Value: 1
Setting | Description |
---|---|
1 | Fahrenheit |
0 | Celsius |
Group1 Temperature Delta Autosend Threshold (how many degree change from the last autosend) Size: 1 Byte, Default Value: 10
Setting | Description |
---|---|
1 - 200 | In tenths of degrees |
Group1 Periodic Temperature Send Interval (minutes) Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
1 - 120 | Temperature Send Interval (minutes) |
0 | Disabled |
Hardware Platform | ZM5202 |
Device Type | Notification Sensor |
Network Operation | Reporting Sleeping Slave |
Firmware Version | HW: 2 FW: 1.40 |
Z-Wave Version | 6.51.07 |
Certification ID | ZC10-17115888 |
Z-Wave Product Id | 0x0010.0x5253.0x5433 |
Color | White |
Firmware Updatable | Updatable by Consumer by RF |
Sensors | Air TemperatureHumidity |
Frequency | XXfrequency |
Maximum transmission power | XXantenna |