This is a
1. Hold F1 to choose interface for Add or Remove Z-Wave network.
2. Click F2 five times until arrows icon turns blue
3. Hold F2 and the device enters into learning mode, then radio icon turns blue and the device is added into Z-Wave network.
MCOHome A8-9 is a Z-Wave enabled multiple environmental monitoring sensor, with 3.5 inch TFT clear display and compliant to Z-Wave Plus standard. It is built in with Temperature, Humidity, PM2.5, CO2, VOC, PIR, illumination, Noise, Smoke sensor. Device can be added into any Z-Wave network, and is compatible with any other Z-Wave certified devices.
Device is suggested to be installed indoor, a place with around 1.5m height above the floor where represents the average CO2 concentration. It should be away from direct sunlight, any cover, or any heat source, to avoid false signal for temperature control.
Power on/off
Wire the adaptor and the device is powered on. It will display all detected information by the sensors.
Display interface
Hold Key F1 can switch among the following 4 display interfaces:
1. Data detecting: display all sensors data
2. Network: Z-Wave Add/Remove
3. Data calibration: to calibrate the detected data manually
4. Local time setting
Data Calibration
1. Hold F1 to choose interface for data calibration.
2. Then hold F2 to switch among the sensors.
3. Choose one and click F2, F1 to change the data.
4. After finished, hold F1 can return data detecting interface.
Local time setting
1. Hold F1 to choose interface for local time setting.
2. Then hold F2 to switch among Hour-Minute-Second-Year-Month-Date.
3. Click F2, F1 can change the data of flashing item.
4. After finished, hold F1 can return data detecting interface.
Reset to factory default | 1. Press & hold F1 to enter Z-Wave setting interface, then press & hold F1 again to enter parameters setting interface 2. Press & hold F2 to enter setting interface and select default 3. Click F2 3 times and displays OFF-->ON-->OK-->OFF, factory setting is restored. |
Inclusion | 1. Hold F1 to choose interface for Add or Remove Z-Wave network. 2. Click F2 five times until arrows icon turns blue 3. Hold F2 and the device enters into learning mode, then radio icon turns blue and the device is added into Z-Wave network. |
Exclusion | 1. Hold F1 to choose interface for Add or Remove Z-Wave network. 2. Click F2 five times until arrows icon turns blue 3. Hold F2 and the device enters into learning mode, then radio icon turns blue and the device is removed into Z-Wave network. |
NIF | XXXNIF |
Wakeup | XXXWakeupDescription |
Protection | XXXProtection |
FirmwareUpdate | XXXFirmwareUpdate |
SetAssociation | XXXSetAssociation |
Group Number | Maximum Nodes | Description |
---|---|---|
1 | 1 | Lifeline group |
This is the PM2.5 Delta Level which determine when to report the current PM2.5 value. Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 | Indicates Turn off report |
1 - 127 | Indicates to report current PM2.5 value when change >n * 1ug/m3 |
This is the CO2 Delta Level which determines when to report the current CO2 value. Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 | Indicates Turn off report |
1 - 127 | Indicates to report current CO2 value when change > n * 5ppm |
This is the temperature Delta Level which determines when to report the current temperature value. Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 | Indicates Turn off report |
1 - 127 | Indicates to report current temperature value when change > n * 0.5 |
This is the humidity Delta Level which determines when to report the current humidity value. Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 | Indicates Turn off report |
1 - 127 | Indicates to report current humidity value when change >n% |
This is the VOC Delta Level which determines when to report the current VOC value. Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 | Indicates Turn off report |
1 - 127 | n*5ppb Report change |
This is the brightness Delta Level which determines when to report the current brightness value. Size: 2 Byte, Default Value: 0
Setting | Description |
---|---|
0 | Indicates Turn off report |
1 - 32767 | Indicates to report current Illumination value when change >n*1 Lux |
This is the noise Delta Level which determines when to report the current noise value. Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 | Indicates Turn off report |
1 - 127 | Indicates to report current Noise value when change >n*1 dB |
This is the temperature Delta Level which determines when to report the current temperature value. Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 | Indicates Turn off report |
1 | Indicates report change |
Size: 1 Byte, Default Value: 1
Setting | Description |
---|---|
0 | Indicates Turn off report |
1 | Indicates report change |
Size: 2 Byte, Default Value: 60
Setting | Description |
---|---|
0 | Turn off report |
35 - 32767 | Report every n*1s |
Size: 2 Byte, Default Value: 60
Setting | Description |
---|---|
0 | Turn off report |
35 - 32767 | Report every n*1s |
Size: 2 Byte, Default Value: 120
Setting | Description |
---|---|
0 | Turn off report |
35 - 32767 | Report every n*1s |
Size: 2 Byte, Default Value: 120
Setting | Description |
---|---|
0 | Turn off report |
35 - 32767 | Report every n*1s |
Size: 2 Byte, Default Value: 180
Setting | Description |
---|---|
0 | Turn off report |
35 - 32767 | Report every n*1s |
Size: 2 Byte, Default Value: 180
Setting | Description |
---|---|
0 | Turn off report |
35 - 32767 | Report every n*1s |
Size: 2 Byte, Default Value: 180
Setting | Description |
---|---|
0 | Turn off report |
35 - 32767 | Report every n*1s |
Size: 2 Byte, Default Value: 300
Setting | Description |
---|---|
0 | Turn off report |
35 - 32767 | Report every n*1s |
Size: 2 Byte, Default Value: 300
Setting | Description |
---|---|
0 | Turn off report |
35 - 32767 | Report every n*1s |
Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 | °C |
1 | °F |
Size: 1 Byte, Default Value: 100
Setting | Description |
---|---|
0 - 127 | ((n-100)/10)=(-10~2.7)℃ |
-128 (255) - -1 (128) | ((156+n)/10)=(2.8~15.5)℃ |
Size: 2 Byte, Default Value: 20
Setting | Description |
---|---|
0 - 40 | n-20=(-20~20)% |
Size: 2 Byte, Default Value: 500
Setting | Description |
---|---|
0 - 1000 | (n-500)=(-500~500)ppm |
Size: 1 Byte, Default Value: 100
Setting | Description |
---|---|
0 - 127 | n-100=(-100~27)ug/m3 |
-128 (255) - -1 (128) | 156+n=(28~155)ug/m3 |
Size: 2 Byte, Default Value: 5000
Setting | Description |
---|---|
0 - 10000 | n-5000=(-5000~5000)lux |
Size: 1 Byte, Default Value: 100
Setting | Description |
---|---|
0 - 127 | n-100=(-100~27)ppb |
-128 (255) - -1 (128) | 156+n=(28~155)ppb |
Size: 1 Byte, Default Value: 50
Setting | Description |
---|---|
0 - 100 | (n-50)=-50~50 |
Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
85 | Factory Reset |
170 | Restore default Parameter |
Dimensions | 0.1090000x0.1090000x0.0420000 mm |
Weight | 397 gr |
Hardware Platform | ZM5202 |
EAN | 4251295702551 |
IP Class | IP 20 |
Voltage | 12 V |
Device Type | Notification Sensor |
Network Operation | Always On Slave |
Z-Wave Version | 6.71.03 |
Certification ID | ZC10-20096971 |
Z-Wave Product Id | 0x015F.0xA803.0x135A |
Color | White |
Frequency | Europe - 868,4 Mhz |
Maximum transmission power | 5 mW |