Aeon Labs Home Energy Meter Gen5 is a Z-Wave device that can monitor the total amount of electricity of your home.
It can report the wattage energy usage and KWH usage to a Z-Wave Controller (especially a gateway). In near real-time you’ll have a full understanding of how much electricity you use and when you use it.
Products that are Z-Wave certified can be used and communicate with other Z-Wave certified devices. Also a tool that can be programmed, scheduled, controlled and communicated with from anywhere in the world.
Reset to factory default | Press and hold the Action button that you can find on the product's housing for 10 seconds and then release. This procedure should only be used when the primary controller is inoperable. |
Inclusion | Turn the primary controller of Z-Wave network into inclusion mode, short press the product’s Action button that you can find on the product's housing. |
Exclusion | Turn the primary controller of Z-Wave network into exclusion mode, short press the product’s Action button that you can find on the product's housing. |
NIF | XXXNIF |
Wakeup | XXXWakeupDescription |
Protection | XXXProtection |
FirmwareUpdate | XXXFirmwareUpdate |
SetAssociation | XXXSetAssociation |
Group Number | Maximum Nodes | Description |
---|---|---|
1 | 5 | Z-Wave Plus Lifeline. The automatic reports (configured by parameter 101/102/103) can be sent to the associated nodes in association group 1. |
Percentage change in wattage to induce a automatic report for the power report of Clamp 2. Size: 1 Byte, Default Value: 10
Setting | Description |
---|---|
0 - 100 | The available range is 0 to 100. |
To set which report need to be sent in Report group 1. Size: 4 Byte, Default Value: 2
Setting | Description |
---|---|
1 | Report Accumulated kWh of whole HEM |
2 | Report Instantaneous Watts of whole HEM. |
4 | Report Instantaneous Voltage of whole HEM. |
8 | Report Instantaneous Current (Amperes) of whole HEM. |
256 | Report Instantaneous Watts of Channel 1. |
768 | Report Instantaneous Watts of Channel 2. |
2048 | Report Accumulated kWh of Channel 1. |
4096 | Report Accumulated kWh of Channel 2. |
65535 | Report Instantaneous Voltage of Channel 1. |
196608 | Report Instantaneous Voltage of Channel 2. |
524288 | Report Instantaneous Current (Amperes) of Channel 1. |
1048576 | Report Instantaneous Current (Amperes) of Channel 2. |
To set which report need to be sent in Report group 2. Size: 4 Byte, Default Value: 1
Setting | Description |
---|---|
1 | Report Accumulated kWh of whole HEM |
2 | Report Instantaneous Watts of whole HEM. |
4 | Report Instantaneous Voltage of whole HEM. |
8 | Report Instantaneous Current (Amperes) of whole HEM. |
256 | Report Instantaneous Watts of Channel 1. |
768 | Report Instantaneous Watts of Channel 2. |
2048 | Report Accumulated kWh of Channel 1. |
4096 | Report Accumulated kWh of Channel 2. |
65535 | Report Instantaneous Voltage of Channel 1. |
196608 | Report Instantaneous Voltage of Channel 2. |
524288 | Report Instantaneous Current (Amperes) of Channel 1. |
1048576 | Report Instantaneous Current (Amperes) of Channel 2. |
To set which report need to be sent in Report group 3. Size: 4 Byte, Default Value: 0
Setting | Description |
---|---|
1 | Report Accumulated kWh of whole HEM |
2 | Report Instantaneous Watts of whole HEM. |
4 | Report Instantaneous Voltage of whole HEM. |
8 | Report Instantaneous Current (Amperes) of whole HEM. |
256 | Report Instantaneous Watts of Channel 1. |
768 | Report Instantaneous Watts of Channel 2. |
2048 | Report Accumulated kWh of Channel 1. |
4096 | Report Accumulated kWh of Channel 2. |
65535 | Report Instantaneous Voltage of Channel 1. |
196608 | Report Instantaneous Voltage of Channel 2. |
524288 | Report Instantaneous Current (Amperes) of Channel 1. |
1048576 | Report Instantaneous Current (Amperes) of Channel 2. |
Set the interval time of sending report in Report group 1. Size: 4 Byte, Default Value: 5
Setting | Description |
---|---|
0 - 268435456 | Interval Seconds |
Set the interval time of sending report in Report group 2. Size: 4 Byte, Default Value: 120
Setting | Description |
---|---|
0 - 268435456 | Interval Seconds |
Set the interval time of sending report in Report group 3. Size: 4 Byte, Default Value: 120
Setting | Description |
---|---|
0 - 268435456 | Interval Seconds |
Set the energy detection mode for the measure reports of parameter 101 to 103. Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 | Report absolute value for power and energy measurements. |
1 | Report positive/negative power and report the algebraic sum energy |
2 | Report positive/negative power and only report energy positive part (consuming electricity) |
3 | Report positive/negative power and only report energy negative part (generating electricity). |
Partner ID. Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 | Aeon Labs Standard Product |
1 - 127 | Partner ID of Partner Product |
Enable/Disable Lock Configuration. Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 | All configuration parameters are configurable. |
1 | All configuration parameters are not configurable (Locked) |
Reset to default factory setting. Size: 4 Byte, Default Value: 0
Setting | Description |
---|---|
1 | Resets all configuration parameters to default setting. |
1431655765 | Reset the product to default factory setting and be excluded from the Z-wave network |
Enable/disable selective reporting only when power change reaches a certain threshold or percentage set in parameter 4 to 11. Size: 1 Byte, Default Value: 1
Setting | Description |
---|---|
0 | Disable |
1 | Enable. |
Threshold change in wattage to induce a automatic report for total power report. Size: 2 Byte, Default Value: 50
Setting | Description |
---|---|
0 - 60000 | The available range is 0 to 60000. |
Threshold change in wattage to induce a automatic report for the power report of Clamp 1. Size: 2 Byte, Default Value: 50
Setting | Description |
---|---|
0 - 60000 | The available range is 0 to 60000. |
Threshold change in wattage to induce a automatic report for the power report of Clamp 2. Size: 2 Byte, Default Value: 50
Setting | Description |
---|---|
0 - 60000 | The available range is 0 to 60000. |
Percentage change in wattage to induce a automatic report for total power report. Size: 1 Byte, Default Value: 10
Setting | Description |
---|---|
0 - 100 | The available range is 0 to 100. |
Percentage change in wattage to induce a automatic report for the power report of Clamp 1. Size: 1 Byte, Default Value: 10
Setting | Description |
---|---|
0 - 100 | The available range is 0 to 100. |
Dimensions | 29x90x11 mm |
Weight | 18 gr |
Hardware Platform | ZM5202 |
EAN | 1220000012813 |
Device Type | Sub Energy Meter |
Network Operation | Always On Slave |
Z-Wave Version | 6.51.06 |
Certification ID | ZC10-15120010 |
Z-Wave Product Id | 0x0086.0x0002.0x005F |
Frequency | Europe - 868,4 Mhz |
Maximum transmission power | 5 mW |