Quickstart

This is a secure Notification Sensor for XXXQFrequencyName. To run this device please make sure the internal battery is fully charged. To add this device to your network execute the following action:
1) Open the cover by turning it counter-clockwise.2) Remove battery blocker.3) Place the device within the direct range of your Z-Wave controller.4) Set the main controller in (security/non-security) add mode (see the controllers manual).5) Quickly, triple click the TMP button located inside the casing.6) Wait for the adding process to end. 7) Successful adding will be confirmed by the Z-Wave controllers message.8) Close the cover by turning it clockwise.9) Place the sensor onto a surface prone to flooding. Three electrodes underneath the device should evenly touch the surface.



Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law. The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material. Use this equipment only for its intended purpose. Follow the disposal instructions. Do not dispose of electronic equipment or batteries in a fire or near open heat sources.
Attention: This manual is automatically generated from Z-Wave Alliance Product data and may be incomplete. Please refer to the Manufacturers Manual for more information.

Product Description

FIBARO Flood Sensor is a universal, Z-Wave Plus compatible, flood and temperature sensor. The device can be powered using battery, 12/24V DC power supply or both. Flood alarm is sent to the Z-Wave network devices or additionally to any alarm system controller through opening a NC contact using the external power supply. The device has a built-in temperature sensor that allows to monitor ambient temperature. FIBARO Flood Sensor is designed to be placed on the floor or mounted on a wall (in this case Flood Sensor probes should be extended using addition wire). The device has a built-in visual LED indicator and an acoustic alarm. The LED indicator signals flood, operating mode or the Z-Wave network communication range. In addition, the device is equipped with a sensor reporting tilt or movement to the main controller e.g. when someone has taken the Sensor from its original location.FIBARO Flood Sensor is sink-proof, which means it drifts on the water surface and keeps on sending alarm signal in case of substantial inundation of water (if not wired). Flood Sensor is compatible with any Z-Wave or Z-Wave+ Controller.

Reset to factory default 1) Open the cover by turning it counter-clockwise. 2) Make sure the device is powered (either by a battery or a DC power supply).3) Press and hold the TMP button for 15-20 seconds until LED glows yellow (4th menu position).4) Release and click the TMP button to start the reset procedure.5) Successful reset will be confirmed with the LED indicator changing colour to red and an acoustic signal.Use reset procedure only if the primary controller is missing or inoperable.
Inclusion 1) Open the cover by turning it counter-clockwise.2) Remove battery blocker.3) Place the device within the direct range of your Z-Wave controller.4) Set the main controller in (security/non-security) add mode (see the controllers manual).5) Quickly, triple click the TMP button located inside the casing.6) Wait for the adding process to end. 7) Successful adding will be confirmed by the Z-Wave controllers message.8) Close the cover by turning it clockwise.9) Place the sensor onto a surface prone to flooding. Three electrodes underneath the device should evenly touch the surface.
Exclusion 1) Open the cover by turning it counter-clockwise.2) Make sure the device is powered (either by a battery or a DC power supply).3) Place the device within the direct range of your Z-Wave controller.4) Set the main controller in remove mode (see the controllers manual).5) Quickly, triple click the TMP button located inside the casing.6) Wait for the removing process to end.7) Successful removing will be confirmed by the Z-Wave controllers message.
NIF XXXNIF
Wakeup FIBARO Flood Sensor will wake up at a defined time interval and will always try to communicate with the main controller. There is a possibility to wake up the device manually by clicking the TMP button
Protection XXXProtection
FirmwareUpdate XXXFirmwareUpdate
SetAssociation XXXSetAssociation

Association Groups:

Group Number Maximum Nodes Description
1 1 Lifeline reports the device status and allows for assigning single device only (main controller by default).
2 5 Flood Control devices in this group will be switched on or off when flood status changes (done via BASIC SET command frames).
3 5 Flood Alarm is assigned to the device status - devices in this group will receive notification about flood detection or cancellation. Useful for devices that can trigger alarms.
4 5 Tamper Alarm is assigned to the TMP button and tilt sensor - devices in this group will receive a notification when the sensor is moved or the cover is taken off (which normally holds the button). Useful for devices that can trigger alarms. Functionality can be altered by parameter 74.

Configuration Parameters

Parameter 1: Alarm cancellation delay

Determines time period (in seconds) by which a Flood Sensor will retainthe flood state after the flooding itself has ceased. The sensorwill keep on reporting flooding to the main controller. This parametersetting does not affect acoustic and visual alarms, which turn off immediatelyafter flooding ceases.
Size: 2 Byte, Default Value: 0

Setting Description
0 - 3600 (in seconds, each 1s)

Parameter 10: Temperature measurement interval

Time interval (in seconds) between consecutive measurements ofbattery level and temperature (done by built-in temperature sensor).If the temperature differs from previously reported by a value determinedin parameter 12, it will be reported to the Z-Wave controller.In battery mode more significant battery level changes will be reported.Short time intervals mean more frequent communication, whichresults in shortened battery life.After consecutive FAILED and SUCCESSFUL communication attempts,the Sensor will go to standby mode.
Size: 4 Byte, Default Value: 300

Setting Description
1 - 65535 in seconds

Parameter 12: Temperature measurement hysteresis

Determines a minimum temperature change value (insensitivity level),resulting in a temperature report being sent to the main controller, according to the parameter 10 settings.
Size: 2 Byte, Default Value: 50

Setting Description
1 - 1000 each 0.01C

Parameter 2: Acoustic and visual signals On / Off in case of flooding

The parameter allows for deactivation visual and acoustic alarm.Parameter allows for increasing a battery life. Setting changes will notaffect the sensors communication with the main controller - commandsto association groups, alarms and reports will still be sent.
Size: 1 Byte, Default Value: 3

Setting Description
0 acoustic and visual alarms inactive
1 acoustic alarm inactive, visual alarm active
2 acoustic alarm active, visual alarm inactive
3 acoustic and visual alarms active

Parameter 50: Low temperature alarm threshold

The parameter stores a temperature value, below which visual indicatorblinks with a colour determined by a parameter 61 settings. Bydefault the visual indicator blinks blue.
Size: 2 Byte, Default Value: 1500

Setting Description
-10000 - 10000 each 0.01C

Parameter 51: High temperature alarm threshold

The parameter stores a temperature value, above which visual indicatorblinks with a colour determined by the parameter 62 settings. Bydefault the visual indicator blinks red.
Size: 2 Byte, Default Value: 3500

Setting Description
-10000 - 10000 each 0.01C

Parameter 61: Low temperature alarm indicator colour

Parameter stores RGB colour value (see the note below for details).
Size: 4 Byte, Default Value: 255

Setting Description
0 - 16777215 Red 16711680; Green 65280; Blue 255; Yellow 16776960; Turquoise 65535; Orange 16750848; White 16777215; Indicator turned off 0

Parameter 62: High temperature alarm indicator colour

Parameter stores RGB colour value (see the note below for details).NOTEThe main controller interprets colours as a sum of its component colours value. Each colours value is a number from 0 to 255.Indicated colour = 65536RED + 256GREEN + BLUEColourDecimal value Red16711680Green 65280Blue255Yellow16776960Turquoise65535Orange16750848White16777215Indicator turned off 0
Size: 4 Byte, Default Value: 16711680

Setting Description
0 - 16777215 Red 16711680; Green 65280; Blue 255; Yellow 16776960; Turquoise 65535; Orange 16750848; White 16777215; Indicator turned off 0

Parameter 63: Temperature indication using LED visual indicator

Parameter determines visual indicators operation. Setting to 0 turnsthe temperature LED indication off, saving battery life.
Size: 1 Byte, Default Value: 2

Setting Description
0 visual indicator does not indicate the temperature
1 visual indicator indicates the temperature (blink) every Temperature Measurement Interval (parameter 10, constant current and battery) and Wake Up Interval (battery mode)
2 visual indicator indicates the temperature continuously, only in constant power mode

Parameter 7: Requested dimming level / roller blind opening level when sending turn on / open command to 2nd association group devices

Determines the requested on level to be sent to devices from 2ndassociation group upon flood event.
Size: 2 Byte, Default Value: 255

Setting Description
1 - 99 requested level
255 turn a device on

Parameter 73: Temperature measurement compensation

Parameter stores a temperature value to be added to or deductedfrom the current temperature measured by internal temperature sensorin order to compensate the difference between air temperatureand temperature at the floor level.
Size: 2 Byte, Default Value: 0

Setting Description
-10000 - 10000 0.00

Parameter 74: Alarm frame sent to 1st and 4th Association Group activation

(MOVEMENT_TAMPER / BUTTON_TAMPER)The device is able to report tamper alarms resulting from sensors tilt/movement or TMP button state change (e.g. taking off the top cover).
Size: 1 Byte, Default Value: 2

Setting Description
0 tamper alarms inactive
1 button tamper alarm active
2 movement tamper alarm active
3 button and movement tampers alarm active

Parameter 75: Alarms signalization duration

The device is capable of automatically turning off alarm signalizationafter a certain amount of time. Long lasting alarm may reduce batterlife, when constantly signalized.The parameter determines time after which alarm will become quiet- still active but the device will go into battery saving mode. Visual oracoustic alarm will be reactivated after time specified in the parameter76. When alarm status ceases, alarm will be turned off immediately.NOTEParameter 75 is ignored when parameter 2 is set to 0.
Size: 4 Byte, Default Value: 0

Setting Description
0 alarms active indefinitely
1 - 65535 time in seconds

Parameter 76: Alarm signalization reactivation period

Parameter determines a time period after which an alarm will be turnedback on (in case it was turned off by parameter 75 setting). It will alsoresend commands to 2nd and 3rd association groups as if the alarmwas detected again.NOTEIn case a time period set in parameter 76 is shorter than the one specified in parameter75, the device will not quiet the alarm, it will remain active.
Size: 4 Byte, Default Value: 0

Setting Description
0 alarm reactivation inactive
1 - 65535 time in seconds

Parameter 77: Flood sensor functionality turned off

Allows to turn off the internal flood sensor. Tamper and built in temperaturesensor will remain active.
Size: 1 Byte, Default Value: 0

Setting Description
0 Default flood sensor operation (flood detection, reactions)
1 Built-in flood sensor TURNED OFF (does not change its state in the main controller, does not send alarm notifications nor turn on/off commands to 2nd/3rd association groups with flood state changes. Always visible in the main controller as turned off)

Parameter 78: Associations in Z-Wave network security mode

This parameter defines how commands are sent in specified associationgroups: as secure or non-secure. Parameter is active only in Z-Wavenetwork security mode. It does not apply to 1st Lifeline group.
Size: 1 Byte, Default Value: 7

Setting Description
0 acoustic and visual alarms inactive
0 none of the groups sent as secure
1 2nd group, Control, sent as secure
1 acoustic alarm inactive, visual alarm active
2 acoustic alarm active, visual alarm inactive
2 3rd group, Alarm, sent as secure
3 acoustic and visual alarms active
4 4th group, Tamper, sent as secure

Parameter 9: Deactivate turning off devices in 2nd association group & alarm cancellation in 3rd group

This setting decides whether device turn off commands and alarmcancellation notifications will be sent to devices in 2nd and 3rd associationgroups (respectively)Setting the parameters value to 0 disables sending these two commandsto associated devices. This means that these devices WILL NOTbe informed when the flooding has ceased. It is still possible to cancelalarms in 3rd association group by choosing second (green) menuposition (see Menu & visual indications on page 10).
Size: 1 Byte, Default Value: 1

Setting Description
0 alarm (flooding) cancellation inactive
1 alarm (flooding) cancellation active

Technical Data

Hardware Platform ZM5202
Device Type Notification Sensor
Network Operation Reporting Sleeping Slave
Firmware Version HW: 1 FW: 3.03:03.03
Z-Wave Version 6.51.07
Certification ID ZC10-18015962
Z-Wave Product Id 0x010F.0x0B01.0x2002
Supported Notification Types Water Alarm
Color White
Firmware Updatable Updatable by Consumer by RF
Sensors Air Temperature
Frequency XXfrequency
Maximum transmission power XXantenna
U.S. / Canada / MexicoNotification Sensor