Parameter 3: Reports type
Parameters value shoud be set to 1 if the module operates in Venetian Blind mode.
Size: 1 Byte, Default Value: 0
Setting |
Description |
0 |
Blind position reports sent to the main controller using Z-Wave Command Class. |
1 |
Blind position reports sent to the main controller using Fibar Command Class. |
Parameter 10: Roller Shutter operating modes
Size: 1 Byte, Default Value: 1
Setting |
Description |
0 |
Roller Blind Mode, without positioning |
1 |
Roller Blind Mode, with positioning |
2 |
Venetian Blind Mode, with positioning |
3 |
Gate Mode, without positioning |
4 |
Gate Mode, with positioning |
Parameter 12: Venetian Blind Mode - time of full turn of the slats
In Gate Mode (parameter 10 set to 3 or 4) the parameter defines the COUNTDOWN time, i.e. the time period after which an open gate starts closing. In any other operating mode the parameter value is irrelevant.
Size: 2 Byte, Default Value: 150
Setting |
Description |
0 |
gate will not close automatically |
1 - 65535 |
(0.01-655.35s, 0.01 step) |
Parameter 13: Set slats back to previous position
In Venetian Blind Mode (parameter 10 set to 2) the parameter influences slats positioning in various situations. In any other operating mode the parameter value is irrelevant.
Size: 1 Byte, Default Value: 1
Setting |
Description |
0 |
Slats return to previously set position only in case of the main controller operation. |
1 |
Slats return to previously set position in case of the main controller operation, momentary switch operation, or when the limit switch is reached. |
Parameter 14: Switch type
Size: 1 Byte, Default Value: 0
Setting |
Description |
0 |
momentary switches |
1 |
toggle switches |
2 |
single, momentary switch (the switch should be connected to S1 terminal) |
Parameter 17: Roller Blind Mode and Venetian Blind Mode - turning off relays after reaching a limit switch
In Gate Mode (parameter 10 set to 3 or 4) the parameter determines a time period after which a gate will start closing after a S2 contact has been disconnected. In this mode, time to turn off the Roller Shutter relays after reaching a limit switch is set to 3 seconds and cannot be modified.
Size: 1 Byte, Default Value: 10
Setting |
Description |
0 |
gate will not close automatically |
1 - 255 |
(0.1-25.5s, 0.1 step) |
Parameter 18: Motor operation detection
Power threshold to be interpreted as reaching a limit switch.
Size: 1 Byte, Default Value: 10
Setting |
Description |
0 |
reaching a limit switch will not be detecte |
1 - 255 |
(1-255W) |
Parameter 22: Motor operation time
Time period for the motor to continue operation.
Size: 2 Byte, Default Value: 240
Setting |
Description |
0 |
function is disabled |
1 - 65535 |
(1-65535s) |
Parameter 29: Forced Roller Shutter calibration
By modifying the parameters setting from 0 to 1 a Roller Shutter 2 enters the calibration mode. The parameter relevant only if a Roller Shutter is set to work in positioning mode (parameter 10 set to 1, 2 or 4).
Size: 1 Byte, Default Value: 0
Setting |
Description |
1 |
start calibration process |
Parameter 30: Response to General Alarm
Size: 1 Byte, Default Value: 2
Setting |
Description |
0 |
no reaction |
1 |
open blind |
2 |
close blind |
Parameter 31: Response to Flood Alarm
Size: 1 Byte, Default Value: 0
Setting |
Description |
0 |
no reaction |
1 |
open blind |
2 |
close blind |
Parameter 32: Response to Smoke, CO and CO2 Alarm
Size: 1 Byte, Default Value: 1
Setting |
Description |
0 |
no reaction |
1 |
open blind |
2 |
close blind |
Parameter 33: Response to Temperature Alarm
Size: 1 Byte, Default Value: 1
Setting |
Description |
0 |
no reaction |
1 |
open blind |
2 |
close blind |
Parameter 35: Managing slats in response to alarm.
In Venetian Blind Mode (parameter 10 set to 2), the parameter determines how the slats will react upon alarm detection. In any other modes, the parameter value is not relevant.
Size: 1 Byte, Default Value: 1
Setting |
Description |
0 |
Do not change slats position – slats return to the last set position. |
1 |
Set slats to their extreme position. |
Parameter 40: Power level report
Power level change that will result in new power value report being sent. The parameter defines a change that needs to occur in order to trigger the report. The value is a percentage of the previous report.
Size: 1 Byte, Default Value: 10
Setting |
Description |
0 |
reports are disabled |
1 - 100 |
(100%) |
Parameter 42: Periodic power or energy reports
This parameter determines a time period between consecutive reports.
Size: 2 Byte, Default Value: 3600
Setting |
Description |
0 |
periodic reports are disabled |
1 - 65534 |
(1-65534s) |
Parameter 43: Energy reports
Energy level change which will result in new energy value report being sent. The parameter defines a change that needs to occur in order to trigger the report.
Size: 1 Byte, Default Value: 10
Setting |
Description |
0 |
reports are disabled |
1 - 254 |
(0.01-2.54kWh) |
Parameter 44: Self-measurement
The device may include power and energy used by itself in reports sent to the main controller.
Size: 1 Byte, Default Value: 0
Setting |
Description |
0 |
self-measurement inactive |
1 |
self-measurement active |
Parameter 50: Scenes/associations activation
Parameter determines whether scenes or associations are activated by the switch buttons.
Size: 1 Byte, Default Value: 0
Setting |
Description |
0 |
associations activation |
1 |
scenes activation |