Quickstart

This is a secure HVAC-Thermostat for Europe. To run this device please connect it to your mains power supply. To add this device to your network execute the following action:

SmartStart Inclusion

1. Scan QR code on device label and add S2 DSK to Provisioning List in Gateway (hub)
2. Connect the device to the power supply (with the temperature sensor already connected).
3. Inclusion will be initiated automatically within few seconds of connection to the power supply and the device will automatically enroll in your network (when the device is excluded and connected to the power supply it automatically enters the LEARN MODE state).

Classic Inclusion

1. Enable add/remove mode on your Z-Wave gateway (hub)
2. Connect the device to the power supply (with the temperature sensor already connected*)
3. Toggle the switch connected to the I1 terminal 3 times within 3 seconds (The device has to get On/Off signal 3 times, meaning 3 times click on the push button or with the normal button 3 times On/Off.) (this procedure puts the device in LEARN MODE) in the first minute after power cycle.
OR
If the device is powered by 24 V SELV supply, press and hold the S (Service) button between 3 and 6 seconds (this procedure puts the device in LEARN MODE)
4. A new device will appear on your dashboard
5. Inclusion with the switch connected to I1 terminal is not limited by time
*If connecting the temperature sensor, switch off the power supply.



Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law. The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material. Use this equipment only for its intended purpose. Follow the disposal instructions. Do not dispose of electronic equipment or batteries in a fire or near open heat sources.

What is Z-Wave?

Z-Wave is the international wireless protocol for communication in the Smart Home. This device is suited for use in the region mentioned in the Quickstart section.

Z-Wave ensures a reliable communication by reconfirming every message (two-way communication) and every mains powered node can act as a repeater for other nodes (meshed network) in case the receiver is not in direct wireless range of the transmitter.

This device and every other certified Z-Wave device can be used together with any other certified Z-Wave device regardless of brand and origin as long as both are suited for the same frequency range.

If a device supports secure communication it will communicate with other devices secure as long as this device provides the same or a higher level of security. Otherwise it will automatically turn into a lower level of security to maintain backward compatibility.

For more information about Z-Wave technology, devices, white papers etc. please refer to www.z-wave.info.

Product Description

The Qubino Flush On/Off Thermostat 2 can measure the power consumption of the connected electrical device and itself has an extremely low power consumption of just 0.4 W.On/Off Thermostat 2 can operate across a wide temperature range, from a chilly -10°C to a scorching 40°C (14 - 104°F) it allows to create complex scenes and switch any device relative to a set temperature range.
- It supports SmartStart inclusion for quick set up- Automatically turn the device on if the temperature is too low (antifreeze)
- Automatically turn the device on/off based on Hysteresis- Works on 110-240 VAC or 24-30 VDC

Prepare for Installation / Reset

Please read the user manual before installing the product.

In order to include (add) a Z-Wave device to a network it must be in factory default state. Please make sure to reset the device into factory default. You can do this by performing an Exclusion operation as described below in the manual. Every Z-Wave controller is able to perform this operation however it is recommended to use the primary controller of the previous network to make sure the very device is excluded properly from this network.

Reset to factory default

This device also allows to be reset without any involvement of a Z-Wave controller. This procedure should only be used when the primary controller is inoperable.

1. Connect the device to the power supply
2. Within the first minute (60 seconds) the device is connected to the power supply, toggle the switch connected to the I1 terminal 5 times within 3 seconds (The device has to get On/Off signal 5 times, meaning 5 times click on the push button or with the normal button 5 times On/Off).
OR
If the device is powered by 24 V SELV supply, press and hold the S (Service) button for more than 6 seconds

Safety Warning for Mains Powered Devices

ATTENTION: only authorized technicians under consideration of the country-specific installation guidelines/norms may do works with mains power. Prior to the assembly of the product, the voltage network has to be switched off and ensured against re-switching.

Installation

The installation process tested and approved by professional electricians, consists of the following simple steps:

Step 1 – Turn OFF the fuse:

• To prevent electrical shock and/or equipment damage, disconnect electrical power at the main fuse or circuit breaker before installation and maintenance.
• Be aware that even if the circuit breaker is off, some voltage may remain in the wires — before proceeding with the installation, be sure no voltage is present in the wiring.
• Take extra precautions to avoid accidentally turning the device on during installation.

Step 2 – Installing the device:

• Connect the device exactly according to the diagrams shown below


N... Neutral wire (+VDC)
L... Live (line) wire (-VDC)
Q⬆... Output for electrical device
I1... Input for switch /push button
TS... Temperature sensor terminal
S... Service button

Connection of the temperature sensor:

The digital temperature sensor comes with a 1 m (3.3 ft) cord and a connector to attach it directly to a Qubino device.

1. To prevent electrical shock, make sure that no voltage is present on the temperature sensor cable.
2. When connected to Qubino device, the temperature sensor is under high voltage, which is very dangerous.
3. Goap d.o.o. does not take responsibility for any damage or electrical shock due to incorrect sensor assembly.
4. The above instructions and description apply to a temperature sensor compatible with Qubino products only.
5. The temperature sensor’s range is between -25 ~ +80°C (-13~ 176°F).

NOTE: When Qubino is wired to 110-240VAC (high voltage) the temperature sensor must not be in direct contact with water.
For more details about the temperature range, see the manual for the temperature sensor below.
Qubino Temperature Sensor manual: https://qubino.com/manuals/Installation/Temperature_Sensor_manual.pdf

Inclusion/Exclusion

On factory default the device does not belong to any Z-Wave network. The device needs to be added to an existing wireless network to communicate with the devices of this network. This process is called Inclusion.

Devices can also be removed from a network. This process is called Exclusion. Both processes are initiated by the primary controller of the Z-Wave network. This controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is then performed doing a special manual action right on the device.

Inclusion

SmartStart Inclusion

1. Scan QR code on device label and add S2 DSK to Provisioning List in Gateway (hub)
2. Connect the device to the power supply (with the temperature sensor already connected).
3. Inclusion will be initiated automatically within few seconds of connection to the power supply and the device will automatically enroll in your network (when the device is excluded and connected to the power supply it automatically enters the LEARN MODE state).

Classic Inclusion

1. Enable add/remove mode on your Z-Wave gateway (hub)
2. Connect the device to the power supply (with the temperature sensor already connected*)
3. Toggle the switch connected to the I1 terminal 3 times within 3 seconds (The device has to get On/Off signal 3 times, meaning 3 times click on the push button or with the normal button 3 times On/Off.) (this procedure puts the device in LEARN MODE) in the first minute after power cycle.
OR
If the device is powered by 24 V SELV supply, press and hold the S (Service) button between 3 and 6 seconds (this procedure puts the device in LEARN MODE)
4. A new device will appear on your dashboard
5. Inclusion with the switch connected to I1 terminal is not limited by time
*If connecting the temperature sensor, switch off the power supply.

Exclusion

1. Connect the device to the power supply
2. Make sure the device is within direct range of your Z-Wave gateway (hub) or use a hand-held Z-Wave remote to perform exclusion
3. Enable add/remove mode on your Z-Wave gateway (hub)
4. Toggle the switch connected to the I1 terminal 3 times within 3 seconds in the first minute after power cycle (The device has to get On/Off signal 3 times, meaning 3 times click on the push button or with the normal button 3 times On/Off).
OR
If the device is powered by 24 V SELV supply, press and hold the S (Service) button between 3 and 6 seconds
5. Exclusion with the switch connected to I1 terminal is not limited by time
6. The device will be removed from your network, but any custom configuration parameters will not be erased

Quick trouble shooting

Here are a few hints for network installation if things dont work as expected.

  1. Make sure a device is in factory reset state before including. In doubt exclude before include.
  2. If inclusion still fails, check if both devices use the same frequency.
  3. Remove all dead devices from associations. Otherwise you will see severe delays.
  4. Never use sleeping battery devices without a central controller.
  5. Dont poll FLIRS devices.
  6. Make sure to have enough mains powered device to benefit from the meshing

Association - one device controls an other device

Z-Wave devices control other Z-Wave devices. The relationship between one device controlling another device is called association. In order to control a different device, the controlling device needs to maintain a list of devices that will receive controlling commands. These lists are called association groups and they are always related to certain events (e.g. button pressed, sensor triggers, ...). In case the event happens all devices stored in the respective association group will receive the same wireless command wireless command, typically a 'Basic Set' Command.

Association Groups:

Group Number Maximum Nodes Description
1 5 Lifeline
2 5 Basic set: triggered by change of output Q
3 5 Basic set: triggered when actual temperature reaches Too High or Too Low temperature limit;
Heat mode: when temperature reaches Too High Temperature Limit reports OFF (0x00), when temperature reaches Too Low Temperature Limit reports ON (0xFF).
Cool mode: when temperature reaches Too High Temperature Limit reports ON (0xFF), when temperature reaches Too Low Temperature Limit reports OFF (0x00).
Thermostat off mode reports OFF (0x00) on both limits reached. Hysteresis is 1C.
4 5 Sensor multilevel report: triggered by change of temperature for threshold defined in configuration parameter 120

Configuration Parameters

Z-Wave products are supposed to work out of the box after inclusion, however certain configuration can adapt the function better to user needs or unlock further enhanced features.

IMPORTANT: Controllers may only allow configuring signed values. In order to set values in the range 128 ... 255 the value sent in the application shall be the desired value minus 256. For example: To set a parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56. In case of a two byte value the same logic applies: Values greater than 32768 may needed to be given as negative values too.

Parameter 1: Input I1 switch type

With this parameter, you can select between push-button (momentary) and on/off toggle switch types.
Size: 1 Byte, Default Value: 1

Setting Description
0 push-button (momentary)
1 on/off toggle switch

Parameter 4: Input 1 contact type

This parameter determines how the switch or push-button is connected.
Size: 1 Byte, Default Value: 0

Setting Description
0 NO (normally open) input type
1 NC (normally close) input type

Parameter 40: Watt Power Consumption Reporting Threshold for Q Load

Choose by how much power consumption needs to increase or decrease to be reported.
Size: 1 Byte, Default Value: 10

Setting Description
0 Power consumption reporting disabled
1 - 100 1% - 100% Power consumption reporting enabled. New value is reported only when Wattage in real time changes by more than the percentage value set in this parameter compared to the previous Wattage reading, starting at 1% (the lowest value possible).

Parameter 42: Watt Power Consumption Reporting Time Threshold for Q

Set value refers to the time interval with which power consumption in Watts is reported (3032767 seconds) starting from time of last Watts reported. If for example 300 is entered, energy consumption reports will be sent to the gateway (hub) every 300 seconds (or 5 minutes).
Size: 2 Byte, Default Value: 600

Setting Description
0 Power consumption reporting disabled
0 - 450 This parameter defines minimum temperature difference between real measured temperature and set-point temperature to turn device on in heat mode or turn device off in cool mode.

Parameter 43: Hysteresis Upper temperature offset

This parameter defines minimum temperature difference between real measured temperature and set-point temperature to turn device on in heat mode or turn device off in cool mode.
NOTE1: If configuration parameter 78 (Scale selection) is set to Celsius, then valid interval is 0250 (0.0 C25.0 C, resolution 0.1 C)
NOTE2: If configuration parameter 78 (Scale selection) is set to Fahrenheit, then valid interval is 0450 (0.0 F45.0 F, resolution 0.1 F) NOTE3: If configuration parameter 78 (Scale selection) is set to Fahrenheit, note that Fahrenheit values will be converted to Celsius degrees. Due to conversion algorithm please be advised that configuration value could drift when converting values back and forth.

Size: 2 Byte, Default Value: 5

Setting Description
0 - 450 This parameter defines minimum temperature difference between real measured temperature and set-point temperature to turn device on in heat mode or turn device off in cool mode.

Parameter 44: Hysteresis Lower temperature offset

This parameter defines minimum temperature difference between real measured temperature and set-point temperature to turn device off in heat mode or turn device on in cool mode.
NOTE1: If configuration parameter 78 (Scale selection) is set to Celsius, then valid interval is 0250 (0.0 C25.0 C, resolution 0.1 C)
NOTE2: If configuration parameter 78 (Scale selection) is set to Fahrenheit, then valid interval is 0450 (0.0 F45.0 F, resolution 0.1 F)
NOTE3: If configuration parameter 78 (Scale selection) is set to Fahrenheit, note that Fahrenheit values will be converted to Celsius degrees. 
Due to conversion algorithm please be advised that configuration value could drift when converting values back and forth.

Size: 2 Byte, Default Value: 5

Setting Description
0 - 450 This parameter defines minimum temperature difference between real measured temperature and set-point temperature to turn device off in heat mode or turn device on in cool mode.

Parameter 45: Antifreeze

Set value determines at which temperature the device will be turned on even (if the thermostat was manually set to off). 
NOTE1: Antifreeze is activated only in heating mode and it uses hysteresis of 0.5C. 
NOTE2: If configuration parameter 78 (Scale selection) is set to Celsius, then valid interval is -125125 (-12.5 C12.5 C, resolution 0.1 C)
NOTE3: If configuration parameter 78 (Scale selection) is set to Fahrenheit, then valid interval is 95545 (9.5 F54.5 F, resolution 0.1 F)
NOTE4: If configuration parameter 78 (Scale selection) is set to Fahrenheit, note that Fahrenheit values will be converted to Celsius degrees. 
Due to conversion algorithm please be advised that configuration value could drift when converting values back and forth.

Size: 2 Byte, Default Value: 50

Setting Description
-125 - 545 Set value determines at which temperature the device will be turned on even (if the thermostat was manually set to off).
1000 Antifreeze functionality disabled.

Parameter 59: Thermostat mode

This parameter determines how the device will operate if it will operate in the heating mode or in the cooling mode. The range of the hysteresis will remain the same, only operation will change from heating to cooling and vice versa
NOTE1: After parameter change, first exclude device (without setting parameters to default value) and then re-include the device!

Size: 1 Byte, Default Value: 0

Setting Description
0 Heat mode
1 Cool mode

Parameter 60: Too low temperature limit

This parameter determines the temperature at which the device sends a command to the associated device - to turn ON device or to turn OFF device:
NOTE1: Too low temperature limit is used with Association Group 3.
NOTE2: If configuration parameter 78 (Scale selection) is set to Celsius, then valid interval is -1501000 (-15.0 C100.0 C, resolution 0.1 C)
NOTE3: If configuration parameter 78 (Scale selection) is set to Fahrenheit, then valid interval is 502120 (5.0 F212.0 F, resolution 0.1 F)
NOTE4: If configuration parameter 78 (Scale selection) is set to Fahrenheit, note that Fahrenheit values will be converted to Celsius degrees. 
Due to conversion algorithm please be advised that configuration value could drift when converting values back and forth.

Size: 2 Byte, Default Value: 50

Setting Description
-150 - 2120 This parameter determines the temperature at which the device sends a command to the associated device - to turn ON device or to turn OFF device.

Parameter 61: Too high temperature limit

This parameter determines the temperature at which the device sends a command to the associated device, to turn ON device or to turn OFF device.
NOTE1: Too high temperature limit is used with Association Group 3.
NOTE2: If configuration parameter 78 (Scale selection) is set to Celsius, then valid interval is 11000 (0.1 C100.0 C, resolution 0.1 C)
NOTE3: If configuration parameter 78 (Scale selection) is set to Fahrenheit, then valid interval is 3222120 (32.2 F212.0 F, resolution 0.1 F)
NOTE4: If configuration parameter 78 (Scale selection) is set to Fahrenheit, note that Fahrenheit values will be converted to Celsius degrees. 
Due to conversion algorithm please be advised that configuration value could drift when converting values back and forth.

Size: 2 Byte, Default Value: 700

Setting Description
1 - 2120 This parameter determines the temperature at which the device sends a command to the associated device, to turn ON device or to turn OFF device.

Parameter 63: Output switch selection

Set value determines the type of the device connected to the on/off output. The output type can be normally open (NO) or normally closed (NC).
Size: 1 Byte, Default Value: 0

Setting Description
0 When switch/device is off the output is 0V (NC)
1 When switch/device is off the output is 240V or 24V (NO).

Parameter 78: Scale Selection

This parameter determines in which measurement unit the device will report temperature (Fahrenheit or Celsius) and determines the scale the configuration parameters (43, 44, 44, 45, 60, 61, 110, 120) are interpreted as.
NOTE1: This scale has influence on Temperature reporting. The device is capable of receiving a Set point in all supported scales.
NOTE2: This configuration parameter has impact on configuration parameters 43, 44, 44, 45, 60, 61, 110, 120.
If scale is set to degrees Fahrenheit configuration values at parameters 43, 44, 44, 45, 60, 61, 110, 120 will be converted to degrees Celsius. Please note that converted values could drift when converting values back and forth.

Size: 1 Byte, Default Value: 0

Setting Description
0 degrees Celsius
1 degrees Fahrenheit

Parameter 110: Temperature Sensor Offset Settings

Set value is added to or subtracted from the actually measured value to adjust the temperature report sent by an external sensor.
NOTE1: If configuration parameter 78 (Scale selection) is set to Celsius, then valid interval is -150150 (-15.0 C15.0 C, resolution 0.1 C)
NOTE2: If configuration parameter 78 (Scale selection) is set to Fahrenheit, then valid interval is -270 - 270 (-27.0 F27.0 F, resolution 0.1 F)
NOTE3: If configuration parameter 78 (Scale selection) is set to Fahrenheit, note that Fahrenheit values will be converted to Celsius degrees. 
Due to conversion algorithm please be advised that configuration value could drift when converting values back and forth.

Size: 2 Byte, Default Value: 0

Setting Description
-270 - 270 Set value is added to or subtracted from the actually measured value to adjust the temperature report sent by an external sensor.

Parameter 120: Temperature Sensor Reporting Threshold

This configuration parameters sets reporting threshold between reported temperature and actual temperature for reporting temperature at association group 4.
NOTE1: If configuration parameter 78 (Scale selection) is set to Celsius, then valid interval is 0150 (0 C15.0 C, resolution 0.1 C)
NOTE2: If configuration parameter 78 (Scale selection) is set to Fahrenheit, then valid interval is 0 - 270 (0 F27.0 F, resolution 0.1 F)
NOTE3: If configuration parameter 78 (Scale selection) is set to Fahrenheit, note that Fahrenheit values will be converted to Celsius degrees. 
Due to conversion algorithm please be advised that configuration value could drift when converting values back and forth.

Size: 2 Byte, Default Value: 5

Setting Description
0 - 270 This configuration parameters sets reporting threshold between reported temperature and actual temperature for reporting temperature at association group 4.

Technical Data

Dimensions 115 x 96 x 22 mm
Weight 50 gr
Hardware Platform ZM5202
EAN 3830062071710
IP Class IP 20
Voltage 230V
Load 10A
Device Type Thermostat - HVAC
Network Operation Always On Slave
Z-Wave Version 6.81.03
Certification ID ZC10-19086722
Z-Wave Product Id 0x0159.0x0005.0x0054
Thermostat Modes CoolHeat
Color Light Blue
Supported Notification Types Power Management
Thermostat Power Source Mains powered (120V/240V)Power Stealing (hard-wired 24V)
Sensors Air Temperature
Electric Load Type Inductive (e.g. Motor)
Switch Type Toggle
Supported Meter Type Electric Energy
Thermostat HVAC Systems Supported Cool OnlyHeat OnlySimple Relay
Frequency Europe - 868,4 Mhz
Maximum transmission power 5 mW

Supported Command Classes

  • Association Grp Info V3
  • Association V2
  • Basic V2
  • Configuration
  • Device Reset Locally
  • Manufacturer Specific V2
  • Meter V4
  • Notification V8
  • Powerlevel
  • Security
  • Security 2
  • Sensor Multilevel V7
  • Supervision
  • Thermostat Mode V3
  • Thermostat Operating State
  • Thermostat Setpoint V3
  • Transport Service V2
  • Version V2
  • Zwaveplus Info V2

Controlled Command Classes

  • Basic V2

Explanation of Z-Wave specific terms

  • Controller — is a Z-Wave device with capabilities to manage the network. Controllers are typically Gateways,Remote Controls or battery operated wall controllers.
  • Slave — is a Z-Wave device without capabilities to manage the network. Slaves can be sensors, actuators and even remote controls.
  • Primary Controller — is the central organizer of the network. It must be a controller. There can be only one primary controller in a Z-Wave network.
  • Inclusion — is the process of adding new Z-Wave devices into a network.
  • Exclusion — is the process of removing Z-Wave devices from the network.
  • Association — is a control relationship between a controlling device and a controlled device.
  • Wakeup Notification — is a special wireless message issued by a Z-Wave device to announces that is able to communicate.
  • Node Information Frame — is a special wireless message issued by a Z-Wave device to announce its capabilities and functions.