Quickstart

This is a secure Binary Power Switch for XXXQFrequencyName. To run this device please connect it to your mains power supply. To add this device to your network execute the following action:
Press the "INKLUSIION" button once.



Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law. The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material. Use this equipment only for its intended purpose. Follow the disposal instructions. Do not dispose of electronic equipment or batteries in a fire or near open heat sources.

Product Description

The Heatit Z-DIN 616, which is built upon the wireless Z-Wave communication protocol, has 6 relay driven outputs and 6 digital inputs. The unit is a multi-purpose Z-Wave I/O module, which can be used for many applications. E.g. Heatit Z-DIN 616 provides the possibility to control other systems via the Z-Wave network, by utilizing the 6 outputs as a kind of handover function to another automation system.
The relay outputs, which can be controlled from the Z-Wave network, is suitable for switching up to 6 pcs. 230Vac loads. In connection with simultaneous connection to SELV (Safety Extra Low Voltage) and 230Vac power circuits for relay outputs, relays must be considered as two groups, where the first group includes output 1 to 3 and the second group includes the outputs 4 to 6. This ensures complete separation between the SELV and 230Vac circuits. If one of the relays in the group is connected to a SELV circuit, the remaining outputs are not allowed to be connected to 230Vac or another circuit which is not a SELV circuit. For example, the relay outputs of the Heatit Z-DIN 616 module can be used to control the 230Vac power supply outlet, making it possible to turn on and disconnect the electrical outlets directly through the Z-Wave network. For safety reasons, however, it is recommended not to use the Heatit Z-DIN 616 to plug electrical outlets that are normally used for hazardous tools and machinery.
The 6 digital inputs of the Heatit Z-DIN 616 are useful for various purposes, where potential-free contacts, or Open Collector outputs, can be connected. The inputs can be configured to different trigger modes; leading edge, trailing edge or level triggered. The Heatit Z-DIN 616’s inputs can be programmed to control other Z-Wave devices when the inputs are activated, by sending Z-Wave commands over the Z-Wave network to e.g. Z-Wave relay modules, dimmer units etc. Heatit Z-DIN 616 allows sending different types of Z-Wave commands by utilizing the different association groups for the 6 inputs. In addition, the Heatit Z-DIN 616 also acts as a repeater, thus extending the range of the Z-Wave network.

Installation

The Heatit Z-DIN 616 must be connected to a 24 Volt AC or DC power supply via the terminals labeled ”Vin”. The polarity is of no importance. The supply must be dimensioned to allow the supplied module with enough power to enable all relays to be activated. Regarding power consumption: see the technical details section.



Relay Output

The 6 outputs of the Heatit Z-DIN 616 module consist of 1-pole SPST connectors (Single-Pole Single-Throw).


As default the outputs are configured to be controlled by its corresponding input (output 1 is controlled by input 1, etc.).
This functionality is changeable via configuration parameter 13 to 18.

Inputs

The digital inputs of the Heatit Z-DIN 616 module can be connected to different types of control signals - switches, relays, open-collector outputs, etc. 
The inputs IN1, IN2, IN3, IN4, IN5 and IN6 which operates as active low, are pr. default pulled up to 3V DC and must be pulled low in order to work, by mounting e.g. a contact between [IN1..IN6] and 0V. The inputs can be configured to different trigger functions using configuration parameters 3 to 8. The default setup of the inputs is switching between the modes on/off, or off/on the leading edge of the input signal, i.e. on each activation of the input, the mode will change (toggle relay function).

Reset to factory default
Resetting is performed by activating the small pushbutton marked ”INCLUSION” located on the front for at least 10 seconds until the LED flashes briefly. E.g. slide a needle pin or a toothpick through the small hole to activate the pushbutton.
Inclusion Press the "INKLUSIION" button once.
Exclusion Press the "INKLUSIION" button once.
NIF XXXNIF
Wakeup XXXWakeupDescription
Protection XXXProtection
FirmwareUpdate XXXFirmwareUpdate
SetAssociation XXXSetAssociation

Association Groups:

Group Number Maximum Nodes Description
1 5 Lifeline
2 5 IN1 Basic Set
3 5 IN1 Switch Binary
4 5 IN1 Multilevel
5 5 IN2 Basic Set
6 5 IN2 Switch Binary
7 5 IN2 Multilevel
8 5 IN3 Basic Set
9 5 IN3 Switch Binary
10 5 IN3 Multilevel
11 5 IN4 Basic Set
3 12 IN4 Switch Binary
13 5 IN4 Multilevel
14 5 IN5 Basic Set
15 5 IN5 Switch Binary
16 5 IN5 Multilevel
17 5 IN6 Basic Set
18 5 IN6 Switch Binary
19 5 IN6 Multilevel

Configuration Parameters

Parameter 1: Status of LED

This parameter can be used to change the mode of the front-mounted status LED.
Size: 1 Byte, Default Value: 1

Setting Description
0 The LED is Off.
2 The LED is steadily lit-up.
2 The LED flashes in 1 second interval (1 Hz).
3 The LED flashes in 1⁄2 second interval (1⁄2 Hz).

Parameter 2: Brightness of status LED

nDetermines the brightness of the status LED.
Size: 1 Byte, Default Value: 50

Setting Description
0 Switch off LED.
1 - 99 Brightness level (%)

Parameter 3: Function setup of input 1

Select the value from the table below. Please refer to the section reg. input functions.
Size: 1 Byte, Default Value: 3

Setting Description
0 Inactive.
1 Mode 1, level-controlled input.
2 Mode 2, falling-edge controlled input.
3 Mode 3, rising-edge controlled input.

Parameter 4: Function setup of input 2

Select the value from the table below. Please refer to the section reg. input functions.
Size: 1 Byte, Default Value: 3

Setting Description
0 Inactive.
1 Mode 1, level-controlled input.
2 Mode 2, falling-edge controlled input.
3 Mode 3, rising-edge controlled input.

Parameter 5: Function setup of input 3

Select the value from the table below. Please refer to the section reg. input functions.
Size: 1 Byte, Default Value: 3

Setting Description
0 Inactive.
1 Mode 1, level-controlled input.
2 Mode 2, falling-edge controlled input.
3 Mode 3, rising-edge controlled input.

Parameter 6: Function setup of input 4

Select the value from the table below. Please refer to the section reg. input functions.
Size: 1 Byte, Default Value: 3

Setting Description
0 Inactive.
1 Mode 1, level-controlled input.
2 Mode 2, falling-edge controlled input.
3 Mode 3, rising-edge controlled input.

Parameter 7: Function setup of input 5

Select the value from the table below. Please refer to the section reg. input functions.
Size: 1 Byte, Default Value: 3

Setting Description
0 Inactive.
1 Mode 1, level-controlled input.
2 Mode 2, falling-edge controlled input.
3 Mode 3, rising-edge controlled input.

Parameter 8: Function setup of input 6

Select the value from the table below. Please refer to the section reg. input functions.
Size: 1 Byte, Default Value: 3

Setting Description
0 Inactive.
1 Mode 1, level-controlled input.
2 Mode 2, falling-edge controlled input.
3 Mode 3, rising-edge controlled input.

Parameter 9: Input Snubber-filter time constant.

Specifies the time used to define the time constant of the input snubber-filter. (Increments in 0.01 second resolution.)
Size: 1 Byte, Default Value: 5

Setting Description
0 - 255 0 - 2,55 seconds

Parameter 10: Threshold value for activation of inputs.

Specifies the time that an entry must be stable before it is accepted as active / idle in 0.01 second resolution.
Size: 1 Byte, Default Value: 20

Setting Description
0 - 255 0 - 2,55 seconds.

Parameter 11: Threshold for input in latched mode

Indicates the time that an input must be activated before it accepts the button latched mode. (Increments in 0.01 second resolution.)
Size: 1 Byte, Default Value: 50

Setting Description
0 - 255 0 - 2,55 seconds.

Parameter 12: Deactivate Central Scene notifications

It is possible to enable Central Scene notifications when the 6 inputs are activated.
Size: 1 Byte, Default Value: 0

Setting Description
0 Central Scene notifications enabled.
1 Central Scene notifications disabled.

Parameter 13: Output function, Output 1

Choose parameter value from the scheme below.
Size: 1 Byte, Default Value: 1

Setting Description
0 Output is controlled via Z-Wave messages.
1 Output is controlled by input 1.

Parameter 14: Output function, Output 2

Choose parameter value from the scheme below.
Size: 1 Byte, Default Value: 1

Setting Description
0 Output is controlled via Z-Wave messages.
1 Output is controlled by input 2.

Parameter 15: Output function, Output 3

Choose parameter value from the scheme below.
Size: 1 Byte, Default Value: 1

Setting Description
0 Output is controlled via Z-Wave messages.
1 Output is controlled by input 3.

Parameter 16: Output function, Output 4

Choose parameter value from the scheme below.
Size: 1 Byte, Default Value: 1

Setting Description
0 Output is controlled via Z-Wave messages.
1 Output is controlled by input 4.

Parameter 17: Output function, Output 5

Choose parameter value from the scheme below.
Size: 1 Byte, Default Value: 1

Setting Description
0 Output is controlled via Z-Wave messages.
1 Output is controlled by input 5.

Parameter 18: Output function, Output 6.

Choose parameter value from the scheme below.
Size: 1 Byte, Default Value: 1

Setting Description
0 Output is controlled via Z-Wave messages.
1 Output is controlled by input 6.

Technical Data

Dimensions 105 x 85 x 60 mm
Weight 240 gr
Hardware Platform ZM5101
EAN 7071236014324
IP Class IP IP 20
Voltage 24 V
Device Type Powered device
Generic Device Class Binary Switch
Specific Device Class Binary Power Switch
Firmware Version 00.07
Z-Wave Version 04.3d
Z-Wave Product Id 0x0234.0x0003.0x0112
Frequency Europe - 868,4 Mhz
Maximum transmission power 5 mW
EuropePowered device