This is a
1.Put primary controller into inclusionmode2.Press any button to wake the One Touch3.Press and hold the middle page button (round button) until the Installer Setup menu appears4.Select the 'Z-Wave' button5.Select the 'Include' button6.Include will fast flash and then SUCCESS will display briefly
Z-Wave is the international wireless protocol for communication in the Smart Home. This device is suited for use in the region mentioned in the Quickstart section.
Z-Wave ensures a reliable communication by reconfirming every message (two-way communication) and every mains powered node can act as a repeater for other nodes (meshed network) in case the receiver is not in direct wireless range of the transmitter.
This device and every other certified Z-Wave device can be used together with any other certified Z-Wave device regardless of brand and origin as long as both are suited for the same frequency range.
If a device supports secure communication it will communicate with other devices secure as long as this device provides the same or a higher level of security. Otherwise it will automatically turn into a lower level of security to maintain backward compatibility.
For more information about Z-Wave technology, devices, white papers etc. please refer to www.z-wave.info.
The Nexia One Touch is a wall controller device that can act as a central scene controller or a traditional stand-alone scene controller.The Nexia One Touch contains up to 15 different scenes organized in 3 pages of screen where each page contains 5 scenes.The Nexia One Touch conveniently runs up to 15 modes and automations with the tap of a button.
Please read the user manual before installing the product.
In order to include (add) a Z-Wave device to a network it must be in factory default state. Please make sure to reset the device into factory default. You can do this by performing an Exclusion operation as described below in the manual. Every Z-Wave controller is able to perform this operation however it is recommended to use the primary controller of the previous network to make sure the very device is excluded properly from this network.
This device also allows to be reset without any involvement of a Z-Wave controller. This procedure should only be used when the primary controller is inoperable.
Please use Factory Reset as a last resort option only as all network settings and associations will be cleared. 1.Press any button to wake the One Touch2.Press and hold the middle page button (round button) until the Installer Setup menu appears3.Select the 'System' button4.Select the 'Factory Reset' button5.Select 'Yes' to proceed with the factory reset
ATTENTION: only authorized technicians under consideration of the country-specific installation guidelines/norms may do works with mains power. Prior to the assembly of the product, the voltage network has to be switched off and ensured against re-switching.
On factory default the device does not belong to any Z-Wave network. The device needs to be added to an existing wireless network to communicate with the devices of this network. This process is called Inclusion.
Devices can also be removed from a network. This process is called Exclusion. Both processes are initiated by the primary controller of the Z-Wave network. This controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is then performed doing a special manual action right on the device.
This device is battery operated and turned into deep sleep state most of the time to save battery life time. Communication with the device is limited. In order to communicate with the device, a static controller C is needed in the network. This controller will maintain a mailbox for the battery operated devices and store commands that can not be received during deep sleep state. Without such a controller, communication may become impossible and/or the battery life time is significantly decreased.
This device will wakeup regularly and announce the wakeup state by sending out a so called Wakeup Notification. The controller can then empty the mailbox. Therefore, the device needs to be configured with the desired wakeup interval and the node ID of the controller. If the device was included by a static controller this controller will usually perform all necessary configurations. The wakeup interval is a tradeoff between maximal battery life time and the desired responses of the device. To wakeup the device please perform the following action: When the backlight and/or screen is off, the first page (round)button press will wake the One Touch causing it to send a Wakeup Notification report.The One Touch has a 6 hour default wakeup interval and will send the Wakeup Notification once that interval expires. WAKEUP_INTERVAL_CAPABILITIES_REPORTMin Wake Up Interval : 4200 secondsMax Wake Up Interval: 86400 secondsDefault Wake Up Interval: 21600 secondsWake Up Interval Step: 10
Here are a few hints for network installation if things dont work as expected.
Z-Wave devices control other Z-Wave devices. The relationship between one device controlling another device is called association. In order to control a different device, the controlling device needs to maintain a list of devices that will receive controlling commands. These lists are called association groups and they are always related to certain events (e.g. button pressed, sensor triggers, ...). In case the event happens all devices stored in the respective association group will receive the same wireless command wireless command, typically a 'Basic Set' Command.
Group Number | Maximum Nodes | Description |
---|---|---|
1 | 2 | Profile: General:LifelineName: Z-Wave Plus LifelineCommand Class List:Battery ReportCentral Scene NotificationDevice Reset Locally Notification |
2 | 2 | Profile: Control: Key1Name: Button1 Basic SetCommand Class List:Basic Set |
3 | 2 | Profile: Control: Key2Name: Button2 Basic SetCommand Class List:Basic Set |
4 | 2 | Profile: Control: Key3Name: Button3 Basic SetCommand Class List:Basic Set |
5 | 2 | Profile: Control: Key4Name: Button4 Basic SetCommand Class List:Basic Set |
6 | 2 | Profile: Control: Key5Name: Button5 Basic SetCommand Class List:Basic Set |
7 | 2 | Profile: Control: Key6Name: Button6 Basic SetCommand Class List:Basic Set |
8 | 2 | Profile: Control: Key7Name: Button7 Basic SetCommand Class List:Basic Set |
9 | 2 | Profile: Control: Key8Name: Button8 Basic SetCommand Class List:Basic Set |
10 | 2 | Profile: Control: Key9Name: Button9 Basic SetCommand Class List:Basic Set |
11 | 2 | Profile: Control: Key10Name: Button10 Basic SetCommand Class List:Basic Set |
12 | 2 | Profile: Control: Key11Name: Button11 Basic SetCommand Class List:Basic Set |
13 | 2 | Profile: Control: Key12Name: Button12 Basic SetCommand Class List:Basic Set |
14 | 2 | Profile: Control: Key13Name: Button13 Basic SetCommand Class List:Basic Set |
15 | 2 | Profile: Control: Key14Name: Button14 Basic SetCommand Class List:Basic Set |
16 | 2 | Profile: Control: Key15Name: Button15 Basic SetCommand Class List:Basic Set |
17 | 2 | Profile: Control: Key1Name: Button1Command Class List:Scene Activation Set |
18 | 2 | Profile: Control: Key2Name: Button2Command Class List:Scene Activation Set |
19 | 2 | Profile: Control: Key3Name: Button3Command Class List:Scene Activation Set |
20 | 2 | Profile: Control: Key4Name: Button4Command Class List:Scene Activation Set |
21 | 2 | Profile: Control: Key5Name: Button5Command Class List:Scene Activation Set |
22 | 2 | Profile: Control: Key6Name: Button6Command Class List:Scene Activation Set |
23 | 2 | Profile: Control: Key7Name: Button7Command Class List:Scene Activation Set |
24 | 2 | Profile: Control: Key8Name: Button8Command Class List:Scene Activation Set |
25 | 2 | Profile: Control: Key9Name: Button9Command Class List:Scene Activation Set |
26 | 2 | Profile: Control: Key10Name: Button10Command Class List:Scene Activation Set |
27 | 2 | Profile: Control: Key11Name: Button11Command Class List:Scene Activation Set |
28 | 2 | Profile: Control: Key12Name: Button12Command Class List:Scene Activation Set |
29 | 2 | Profile: Control: Key13Name: Button13Command Class List:Scene Activation Set |
30 | 2 | Profile: Control: Key14Name: Button14Command Class List:Scene Activation Set |
31 | 2 | Profile: Control: Key15Name: Button15Command Class List:Scene Activation Set |
32 | 2 | Profile: Control: Key1Name: Button1Command Class List:Thermostat Setpoint Set |
33 | 2 | Profile: Control: Key2Name: Button2Command Class List:Thermostat Setpoint Set |
34 | 2 | Profile: Control: Key3Name: Button3Command Class List:Thermostat Setpoint Set |
35 | 2 | Profile: Control: Key4Name: Button4Command Class List:Thermostat Setpoint Set |
36 | 2 | Profile: Control: Key5Name: Button5Command Class List:Thermostat Setpoint Set |
37 | 2 | Profile: Control: Key6Name: Button6Command Class List:Thermostat Setpoint Set |
38 | 2 | Profile: Control: Key7Name: Button7Command Class List:Thermostat Setpoint Set |
39 | 2 | Profile: Control: Key8Name: Button8Command Class List:Thermostat Setpoint Set |
40 | 2 | Profile: Control: Key9Name: Button9Command Class List:Thermostat Setpoint Set |
41 | 2 | Profile: Control: Key10Name: Button10Command Class List:Thermostat Setpoint Set |
42 | 2 | Profile: Control: Key11Name: Button11Command Class List:Thermostat Setpoint Set |
43 | 2 | Profile: Control: Key12Name: Button12Command Class List:Thermostat Setpoint Set |
44 | 2 | Profile: Control: Key13Name: Button13Command Class List:Thermostat Setpoint Set |
45 | 2 | Profile: Control: Key14Name: Button15Command Class List:Thermostat Setpoint Set |
46 | 2 | Profile: Control: Key15Name: Button15Command Class List:Thermostat Setpoint Set |
Z-Wave products are supposed to work out of the box after inclusion, however certain configuration can adapt the function better to user needs or unlock further enhanced features.
IMPORTANT: Controllers may only allow configuring signed values. In order to set values in the range 128 ... 255 the value sent in the application shall be the desired value minus 256. For example: To set a parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56. In case of a two byte value the same logic applies: Values greater than 32768 may needed to be given as negative values too.
Reserved Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 | Reserved |
Configuration for the type of button and which commands it will send when pressed. Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 - 4 | 0x00 = Central Scene0x01 = Scene Control Momentary 0x02 = BASICSET Toggle 0x03 = Scene Control/BASICSET toggle0x04 = Thermostat |
Configuration for the type of button and which commands it will send when pressed. Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 - 4 | 0x00 = Central Scene0x01 = Scene Control Momentary 0x02 = BASICSET Toggle 0x03 = Scene Control/BASICSET toggle0x04 = Thermostat |
Configuration for the type of button and which commands it will send when pressed. Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 - 4 | 0x00 = Central Scene0x01 = Scene Control Momentary 0x02 = BASICSET Toggle 0x03 = Scene Control/BASICSET toggle0x04 = Thermostat |
Configuration for the type of button and which commands it will send when pressed. Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 - 4 | 0x00 = Central Scene0x01 = Scene Control Momentary 0x02 = BASICSET Toggle 0x03 = Scene Control/BASICSET toggle0x04 = Thermostat |
Configuration for the type of button and which commands it will send when pressed. Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 - 4 | 0x00 = Central Scene0x01 = Scene Control Momentary 0x02 = BASICSET Toggle 0x03 = Scene Control/BASICSET toggle0x04 = Thermostat |
Configuration for the type of button and which commands it will send when pressed. Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 - 4 | 0x00 = Central Scene0x01 = Scene Control Momentary 0x02 = BASICSET Toggle 0x03 = Scene Control/BASICSET toggle0x04 = Thermostat |
Configuration for the type of button and which commands it will send when pressed. Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 - 4 | 0x00 = Central Scene0x01 = Scene Control Momentary 0x02 = BASICSET Toggle 0x03 = Scene Control/BASICSET toggle0x04 = Thermostat |
Size: 1 Byte, Default Value: 0
Setting | Description |
---|
Size: 1 Byte, Default Value: 0
Setting | Description |
---|
Size: 1 Byte, Default Value: 0
Setting | Description |
---|
Configuration for the type of button and which commands it will send when pressed. Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 - 4 | 0x00 = Central Scene0x01 = Scene Control Momentary 0x02 = BASICSET Toggle 0x03 = Scene Control/BASICSET toggle0x04 = Thermostat |
Button touch calibration sensitivity level Size: 1 Byte, Default Value: 10
Setting | Description |
---|---|
1 - 10 | 1 = Least Sensitive 10 = Most Sensitive |
Screen contrast level Size: 1 Byte, Default Value: 7
Setting | Description |
---|---|
1 - 10 | 1=less contrast, 10=more contrast |
Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 | Reserved |
Button LED Brightness Level Size: 1 Byte, Default Value: 5
Setting | Description |
---|---|
1 - 10 | 1=10% 10 = 100% |
Backlight Brightness Level Size: 1 Byte, Default Value: 5
Setting | Description |
---|---|
1 - 10 | 1=10% 10 = 100% |
Backlight timeout after a scene (rectangular) button press Size: 1 Byte, Default Value: 10
Setting | Description |
---|---|
10 - 15 | seconds |
Backlight timeout after a page (round) button press Size: 1 Byte, Default Value: 5
Setting | Description |
---|---|
5 - 15 | seconds |
Size: 1 Byte, Default Value: 0
Setting | Description |
---|
Screen timeout- number of minutes after the last button press till the screen goes blank Size: 1 Byte, Default Value: 60
Setting | Description |
---|---|
0 | disabled |
1 - 240 | minutes |
Page to default to after a screen timeout Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 - 3 | 0 = no change, 1=page1, 2=page2, 3=page3 |
Configuration for the type of button and which commands it will send when pressed. Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 - 4 | 0x00 = Central Scene0x01 = Scene Control Momentary 0x02 = BASICSET Toggle 0x03 = Scene Control/BASICSET toggle0x04 = Thermostat |
Battery status shutdown threshold Size: 1 Byte, Default Value: 5
Setting | Description |
---|---|
0 - 20 | % |
Battery % Radio Cutoff Threshold Size: 1 Byte, Default Value: 10
Setting | Description |
---|---|
0 - 40 | % |
Low Battery % Indicator Threshold Size: 1 Byte, Default Value: 20
Setting | Description |
---|---|
5 - 50 | % |
Battery % threshold for midlevel indicator Size: 1 Byte, Default Value: 50
Setting | Description |
---|---|
30 - 80 | % |
Configuration for the type of button and which commands it will send when pressed. Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 - 4 | 0x00 = Central Scene0x01 = Scene Control Momentary 0x02 = BASICSET Toggle 0x03 = Scene Control/BASICSET toggle0x04 = Thermostat |
Configuration for the type of button and which commands it will send when pressed. Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 - 4 | 0x00 = Central Scene0x01 = Scene Control Momentary 0x02 = BASICSET Toggle 0x03 = Scene Control/BASICSET toggle0x04 = Thermostat |
Configuration for the type of button and which commands it will send when pressed. Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 - 4 | 0x00 = Central Scene0x01 = Scene Control Momentary 0x02 = BASICSET Toggle 0x03 = Scene Control/BASICSET toggle0x04 = Thermostat |
Configuration for the type of button and which commands it will send when pressed. Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 - 4 | 0x00 = Central Scene0x01 = Scene Control Momentary 0x02 = BASICSET Toggle 0x03 = Scene Control/BASICSET toggle0x04 = Thermostat |
Configuration for the type of button and which commands it will send when pressed. Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 - 4 | 0x00 = Central Scene0x01 = Scene Control Momentary 0x02 = BASICSET Toggle 0x03 = Scene Control/BASICSET toggle0x04 = Thermostat |
Hardware Platform | ZM5202 |
Device Type | Wall Controller |
Network Operation | Portable Slave |
Firmware Version | 01 |
Z-Wave Version | 6.51.06 |
Certification ID | ZC10-15070012 |
Z-Wave Product Id | 0x0178.0x5343.0x4735 |
Frequency | XXfrequency |
Maximum transmission power | XXantenna |