This is a
S WiDom Universal Double Switch is designed for installation in flush mounting boxes, close to the loads to be controlled. A single click on the Z-Wave button will confirm Inclusion and three clicks will confirm Exclusion. Please read carefully the enclosed user manual before installation of the radio-actuator, in order to ensure an error-free functioning. ATTENTION: only authorized technicians under consideration of the country-specific installation guidelines/norms may do works with 230 Volt mains power.
1) Ensure that the main power switch is set in the OFF position
2) Connect the device following the diagrams provided
3) Include the device into the Z-Wave network
4) Shut the electrical box containing the device
5) Turn the main power switch back on
Universal Double Switch is an ON/OFF control device designed to independently control two separate loads, suited for use as both a local and remote switch. Each of its two channels features an integrated consumption measurement device. The Universal Double Switch also boasts the lowest energy consumption on the market.
INFO: WiDom Universal Double Switch is designed for installation in flush mounting boxes, close to the loads to be controlled.
WARNING: WiDom Universal Double Switch must be installed by electricians qualified to operate on electrical systems in compliance with safety requirements set out by current regulations.
DANGER: WiDom Universal Double Switch must be connected to 230V AC voltage mains supplies; please ensure that the general switch is in the OFF position prior to carrying out any operation.
DANGER: Any operation requiring the use of service button (B) must only be carried out during the installation phase and must be considered as a service procedure to be performed by qualified personnel. This operation must be carried out by adopting all necessary precautions to operate on areas with a single level of isolation.
WARNING: Do not connect loads exceeding the maximum power load permitted by the relay contacts.
WARNING: All connections must be performed according to the electrical diagrams provided.
WARNING: WiDom Universal Double Switch must be installed in norm-compliant systems suitably protected from overloads and short circuits.
TIP: The antenna must not be shortened, removed or modified. To ensure maximum efficiency, it must be installed as shown. Large size metal equipment near the antenna can negatively affect reception. Each WiDom device is a node in a mesh network. If there are metal obstacles, the obstacle can often be overcome with a further triangulation node.
If the device was successfully included it will apear in your SmartHome Software.
WiDom Universal Double Switch can control other devices such as relays or dimmers.
Reset to factory default | XXXResetDescription |
Inclusion |
|
Exclusion |
|
NIF | Single press the Z-Wave Button to send out a Node Information Frame. |
Wakeup | XXXWakeupDescription |
Protection | XXXProtection |
FirmwareUpdate | XXXFirmwareUpdate |
SetAssociation | XXXSetAssociation |
Group Number | Maximum Nodes | Description |
---|---|---|
1 | 8 | LifeLine: Devices to receive notifications on: status changes; instantaneous power level; device local reset |
2 | 8 | On/Off control (Switch 1) |
3 | 8 | Dimming control (Switch 1) |
4 | 8 | On/Off control (Switch 2) |
5 | 8 | Dimming control (Switch 2) |
Defines the status of the output O1/O2 when the switch connected to I1/I2 receives 1 Click. Size: 1 Byte, Default Value: 1
Setting | Description |
---|---|
1 | TOGGLE |
2 | ON: If the initial status is OFF the system switches to ON; conversely, it maintains its status (ON). |
3 | OFF: If the initial status is ON the system switches to OFF; conversely, it maintains its status (OFF). |
4 | IGNORE: The device maintains the initial status |
Defines the status of the output O1/O2 when the switch connected to I1/I2 receives 2 Click. Size: 1 Byte, Default Value: 1
Setting | Description |
---|---|
1 | TOGGLE |
2 | ON: If the initial status is OFF the system switches to ON; conversely, it maintains its status (ON). |
3 | OFF: If the initial status is ON the system switches to OFF; conversely, it maintains its status (OFF). |
4 | IGNORE: The device maintains the initial status |
Defines if the outputs are controlled individually, as a traditional device with two channels, or if its behaviour simulates a single pole double throw relay. Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 | SINGLE CHANNELS: Channel 1 and Channel 2 are controlled individually |
1 - 127 | SINGLE POLE DOUBLE THROW RELAY: The two channels are in opposite status. If the Channel 1 is close the Channel 2 is open, if the Channel 1 is open the Channel 2 is close. The value of the parameter defines the closing delay of the relay in tenth of seconds |
Defines the number of clicks on the Switch 1 or Switch 2 that enable the control of the correspondent associated devices. Size: 1 Byte, Default Value: 2
Setting | Description |
---|---|
1 | Associated devices are controlled by 1 Click on the correspondent external switch |
2 | Associated devices are controlled by 2 Clicks on the correspondent external switch |
Defines how to control the devices associated to group 2 and 3. Size: 1 Byte, Default Value: 100
Setting | Description |
---|---|
0 | The associated devices are switched OFF |
255 | The associated devices are switched ON |
1 - 99 | The associated devices (dimmer, roller shutters) are set to the indicated level (only for devices associated to group 3) |
100 | If the Relay 1 is ON/OFF, the associated devices are ON/OFF |
101 | If the Relay 1 is ON the associated devices are ON; if it is OFF no action is taken on the associated devices |
102 | If the Relay 1 is OFF the associated devices are OFF; if it is ON no action is taken on the associated devices |
103 | If the Relay 1 is ON the associated devices are OFF; if it is OFF no action is taken on the associated devices |
104 | If the Relay 1 is OFF the associated devices are ON; if it is ON no action is taken on the associated devices |
105 | If the Relay 1 is ON/OFF, the associated devices are OFF/ON |
106 | No action is taken on the associated devices |
Defines how to control the devices associated to group 4 and 5. Size: 1 Byte, Default Value: 100
Setting | Description |
---|---|
0 | The associated devices are switched OFF |
255 | The associated devices are switched ON |
1 - 99 | The associated devices (dimmer, roller shutters) are set to the indicated level (only for devices associated to group 5) |
100 | If the Relay 2 is ON/OFF, the associated devices are ON/OFF |
101 | If the Relay 2 is ON the associated devices are ON; if it is OFF no action is taken on the associated devices |
102 | If the Relay 2 is OFF the associated devices are OFF; if it is ON no action is taken on the associated devices |
103 | If the Relay 2 is ON the associated devices are OFF; if it is OFF no action is taken on the associated devices |
104 | If the Relay 2 is OFF the associated devices are ON; if it is ON no action is taken on the associated devices |
105 | If the Relay 2 is ON/OFF, the associated devices are OFF/ON |
106 | No action is taken on the associated devices |
Defines the time after which the Channel 1 is switched ON. Size: 2 Byte, Default Value: 0
Setting | Description |
---|---|
0 | Timer disabled |
1 - 32000 | After this time the relay of the Channel 1 is ON |
Defines the time after which the Channel 2 is switched ON. Size: 2 Byte, Default Value: 0
Setting | Description |
---|---|
0 | Timer disabled |
1 - 32000 | After this time the relay of the Channel 2 is ON |
Defines the time after which the Channel 1 is switched OFF. Size: 2 Byte, Default Value: 0
Setting | Description |
---|---|
0 | Timer disabled |
1 - 32000 | After this time the relay of the Channel 1 is OFF |
Defines the time after which the Channel 2 is switched OFF. Size: 2 Byte, Default Value: 0
Setting | Description |
---|---|
0 | Timer disabled |
1 - 32000 | After this time the relay of the Channel 2 is OFF |
The two channels can be controlled individually by Z-Wave network. The status of the channels upon receipt of a Multi-Channel Basic Set command is defined by the value set on the parameter. Size: 1 Byte, Default Value: 1
Setting | Description |
---|---|
1 | AS RECEIVED |
2 | IGNORE IF ON |
3 | IGNORE IF OFF |
4 | IGNORE |
The channels of the device can be controlled individually from all other Z-Wave devices that support the multichannel feature. In order to support also the integration with no-multichannel systems, this parameter allows to define if the receipt of a no-multichannel command controls only the Channel 1 or both. Size: 1 Byte, Default Value: 3
Setting | Description |
---|---|
1 | The receipt of a Basic Set ON/OFF set the Channel 1 to ON/OFF |
3 | The receipt of a Basic Set ON/OFF set both the Channel 1 and the Channel 2 to ON/OFF |
Defines the status of the device following a restart. Size: 1 Byte, Default Value: 4
Setting | Description |
---|---|
0 | Both Relay 1 and Relay 2 OFF |
1 | Relay 1 ON, Relay 2 OFF |
2 | Relay 1 OFF, Relay 2 ON |
3 | Both Relay 1 and Relay 2 ON |
4 | PREVIOUS STATUS: Status prior to restart |
Defines which parameters should be reset to default values. Size: 1 Byte, Default Value: 4
Setting | Description |
---|---|
0 | The device is reset to the original factory settings |
1 | All associations and only the associations are reset |
2 | The associations are maintained while all other configuration parameters are reset to the original factory settings, except for the specific configuration. |
3 | The device will be restarted |
4 | No action is performed |
Defines the type of external switch connected to the device. Size: 1 Byte, Default Value: 4
Setting | Description |
---|---|
0 | The actions on the external switch are ignored. In this mode, the device can only be controlled via the network. |
1 | The external switch is a normally open button |
2 | The external switch is a traditional switch |
4 | After the first single click on the external switch, the system automatically determines the type of external switch used and sets the parameter with the new value accordingly. |
Dimensions | 0.0370000x0.0370000x0.0170000 mm |
Weight | 28.2 gr |
Hardware Platform | ZM5202 |
EAN | 8059265060047 |
IP Class | IP 20 |
Voltage | 230 V |
Load | 10 A |
Device Type | On/Off Power Switch |
Generic Device Class | Binary Switch |
Specific Device Class | Binary Power Switch |
Firmware Version | 01.28 |
Z-Wave Version | 04.05 |
Certification ID | ZC10-15115003 |
Z-Wave Product Id | 0x0149.0x1214.0x0504 |
Frequency | Europe - 868,4 Mhz |
Maximum transmission power | 5 mW |