This is a
Inclusion: Including the RTH100Z into an Existing Network:1. Set your primary controller to Include mode, to add the RTH100Z as a node on your network (see your controllers user manual for detailed instructions).2. Press and release the Install button. The controller will indicate the device has been included into the network.Your controller will indicate the RTH100Z was successfully added to its network (see your controllers user manual for details).Inclusion and exclusion are always done at normal transmit power mode.If your controller supports NWI, then you can optionally set the primary to NWI include mode. Please note that NWI inclusion mode does not end when you have included a new node.This allows multiple nodes to be included without having to physically go back to the controller to initiate the next inclusion.Therefore you must manually terminate NWI inclusion mode at the controller when you have finished including any new nodes to the network.Since intermediate included nodes will assist the inclusion process by routing messages, we recommend that nodes close to the primary controller be installed first, proceeding out in consecutive rings from the controller.Note: Consult your controllers user manual for details on removing a device from a Z-Wave network.
Z-Wave is the international wireless protocol for communication in the Smart Home. This device is suited for use in the region mentioned in the Quickstart section.
Z-Wave ensures a reliable communication by reconfirming every message (two-way communication) and every mains powered node can act as a repeater for other nodes (meshed network) in case the receiver is not in direct wireless range of the transmitter.
This device and every other certified Z-Wave device can be used together with any other certified Z-Wave device regardless of brand and origin as long as both are suited for the same frequency range.
If a device supports secure communication it will communicate with other devices secure as long as this device provides the same or a higher level of security. Otherwise it will automatically turn into a lower level of security to maintain backward compatibility.
For more information about Z-Wave technology, devices, white papers etc. please refer to www.z-wave.info.
Remote Temperature and Humidity Sensor for HVAC market
Please read the user manual before installing the product.
In order to include (add) a Z-Wave device to a network it must be in factory default state. Please make sure to reset the device into factory default. You can do this by performing an Exclusion operation as described below in the manual. Every Z-Wave controller is able to perform this operation however it is recommended to use the primary controller of the previous network to make sure the very device is excluded properly from this network.
This device also allows to be reset without any involvement of a Z-Wave controller. This procedure should only be used when the primary controller is inoperable.
Factory Reset To reset the RTH100Zs configurations and Z-Wave parameters to Factory Settings (Including association groups and scene configurations), and remove the RTH100Z from any Z-Wave network: Note: Please use this procedure only when the network primary controller is missing or otherwise inoperable1. Hold down the Install button for approximately 10 seconds 2. Release the install button (the RTH100Z will reset all internal configuration including z-wave configurations). The unit will then reset. 3. When the Status LED begins to blink (un-enrolled) the unit has finished restoring configurations is running in normal mode.
On factory default the device does not belong to any Z-Wave network. The device needs to be added to an existing wireless network to communicate with the devices of this network. This process is called Inclusion.
Devices can also be removed from a network. This process is called Exclusion. Both processes are initiated by the primary controller of the Z-Wave network. This controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is then performed doing a special manual action right on the device.
This device is battery operated and turned into deep sleep state most of the time to save battery life time. Communication with the device is limited. In order to communicate with the device, a static controller C is needed in the network. This controller will maintain a mailbox for the battery operated devices and store commands that can not be received during deep sleep state. Without such a controller, communication may become impossible and/or the battery life time is significantly decreased.
This device will wakeup regularly and announce the wakeup state by sending out a so called Wakeup Notification. The controller can then empty the mailbox. Therefore, the device needs to be configured with the desired wakeup interval and the node ID of the controller. If the device was included by a static controller this controller will usually perform all necessary configurations. The wakeup interval is a tradeoff between maximal battery life time and the desired responses of the device. To wakeup the device please perform the following action: To wake-up the device for configuration you can triple-press the install button.
Here are a few hints for network installation if things dont work as expected.
Z-Wave devices control other Z-Wave devices. The relationship between one device controlling another device is called association. In order to control a different device, the controlling device needs to maintain a list of devices that will receive controlling commands. These lists are called association groups and they are always related to certain events (e.g. button pressed, sensor triggers, ...). In case the event happens all devices stored in the respective association group will receive the same wireless command wireless command, typically a 'Basic Set' Command.
Group Number | Maximum Nodes | Description |
---|---|---|
1 | 1 | Z-Wave Plus Lifeline |
2 | 5 | Temperature Reports |
3 | 5 | Humidity Reports |
4 | 5 | Temperature driven BASIC_SETs |
5 | 5 | Humidity driven BASIC_SETs |
6 | 5 | Battery Reports |
Z-Wave products are supposed to work out of the box after inclusion, however certain configuration can adapt the function better to user needs or unlock further enhanced features.
IMPORTANT: Controllers may only allow configuring signed values. In order to set values in the range 128 ... 255 the value sent in the application shall be the desired value minus 256. For example: To set a parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56. In case of a two byte value the same logic applies: Values greater than 32768 may needed to be given as negative values too.
Time between sending Battery Reports in Hours Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
1 - 127 | 1127 hours |
0 | Disabled |
Group2 Temperature Delta Autosend Threshold (how many degree change from the last autosend) Size: 1 Byte, Default Value: 10
Setting | Description |
---|---|
1 - 50 | In tenths of degrees |
0 | Disabled |
Group2 Periodic Temperature Send Interval (minutes) Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
1 - 120 | Minutes |
0 | Disabled |
Send Basic Set On above humidity See also Register 20 Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 - 100 | Percent |
0 | Disabled |
Send Basic Set On below humidity See also Register 20 Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 - 100 | Percent |
0 | Disabled |
Send Basic Set Off above humidity See also Register 20 Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 - 100 | Percent |
0 | Disabled |
Send Basic Set Off below humidity See also Register 20 Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 - 100 | Percent |
0 | Disabled |
Group1- Humidity Delta Autosend Threshold (how many degree change from the last autosend) Size: 1 Byte, Default Value: 5
Setting | Description |
---|---|
1 - 50 | Percent |
Group1- Periodic Humidity Send Interval Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
1 - 120 | Minutes |
0 | Disabled |
Group3- Humidity Delta Autosend Threshold (how many degree change from the last autosend) Size: 1 Byte, Default Value: 5
Setting | Description |
---|---|
1 - 30 | Percent |
0 | Disabled |
Group3- Periodic Humidity Send Interval (minutes) Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
1 - 120 | Minutes |
0 | Disabled |
Send Basic Set On above temp See also Register 20 Size: 1 Byte, Default Value: 121
Setting | Description |
---|---|
15 - 120 | 15120 Degrees F |
121 | Disabled |
Basic Set Options for Temp and Humidity Size: 1 Byte, Default Value: 1
Setting | Description |
---|---|
2 | Enable Configuration Registers 2, 5, 13, 14 |
1 | Enable Configuration Registers 2, 5, 12, 15 |
3 | Enable Configuration Registers 3, 4, 12, 15 |
4 | Enable Configuration Registers 3, 4, 13, 14 |
Temp offset Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
249 - 7 | Degrees(-7 to 7) |
Humidity offset Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
249 - 7 | Percent(-7 to 7) |
Humidity Filter Time Constant Size: 1 Byte, Default Value: 30
Setting | Description |
---|---|
1 - 60 | Minutes |
Send Basic Set On above temp See also Register 20 Size: 1 Byte, Default Value: 121
Setting | Description |
---|---|
15 - 120 | 15120 Degrees F |
121 | Disabled |
Send Basic Set On below temp See also Register 20 Size: 1 Byte, Default Value: 121
Setting | Description |
---|---|
15 - 120 | 15120 Degrees F |
121 | Disabled |
Send Basic Set Off below temp See also Register 20 Size: 1 Byte, Default Value: 121
Setting | Description |
---|---|
15 - 120 | 15120 Degrees F |
121 | Disabled |
Make multiple attempts for all Basic Set Commands Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
1 - 5 | Number of extra attempts sent every minute after first send |
0 | Disabled |
Temp Units Size: 1 Byte, Default Value: 1
Setting | Description |
---|---|
1 | Fahrenheit |
0 | Celsius |
Group1 Temperature Delta Autosend Threshold (how many degree change from the last autosend) Size: 1 Byte, Default Value: 10
Setting | Description |
---|---|
1 - 200 | In tenths of degrees |
Group1 Periodic Temperature Send Interval (minutes) Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
1 - 120 | Temperature Send Interval (minutes) |
0 | Disabled |
Hardware Platform | ZM5202 |
Device Type | Notification Sensor |
Network Operation | Reporting Sleeping Slave |
Firmware Version | HW: 2 FW: 1.40 |
Z-Wave Version | 6.51.07 |
Certification ID | ZC10-17115888 |
Z-Wave Product Id | 0x0010.0x5253.0x5433 |
Color | White |
Firmware Updatable | Updatable by Consumer by RF |
Sensors | Air TemperatureHumidity |
Frequency | XXfrequency |
Maximum transmission power | XXantenna |