This is a
Inclusion: Including the REM50Z into an Existing Network:1. Set your primary controller to Include mode, to add the REM50Z as a node on your network(see your controllers user manual for detailed instructions).2. Press the Install button. The controller will indicate the device has been included into the network.Your controller will indicate the REM50Z was successfully added to its network (see your controllers user manual for details). Inclusion and exclusion are always done at normal transmit power mode.If your controller supports NWI, then you can optionally set the primary to NWI include mode. Please note that NWI inclusion mode does not end when you have included a new node. This allows multiple nodes to be included without having to physically go back to the controller to initiate the next inclusion. Therefore you must manually terminate NWI inclusion mode at the controller when you have finished including any new nodes to the network. Since intermediate included nodes will assist the inclusion process by routing messages, we recommend that nodes close to the primary controller be installed first, proceeding out in consecutive rings from the controller.Note: Consult your controllers user manual for details on removing a device from a Z-Wave network.
Z-Wave is the international wireless protocol for communication in the Smart Home. This device is suited for use in the region mentioned in the Quickstart section.
Z-Wave ensures a reliable communication by reconfirming every message (two-way communication) and every mains powered node can act as a repeater for other nodes (meshed network) in case the receiver is not in direct wireless range of the transmitter.
This device and every other certified Z-Wave device can be used together with any other certified Z-Wave device regardless of brand and origin as long as both are suited for the same frequency range.
If a device supports secure communication it will communicate with other devices secure as long as this device provides the same or a higher level of security. Otherwise it will automatically turn into a lower level of security to maintain backward compatibility.
For more information about Z-Wave technology, devices, white papers etc. please refer to www.z-wave.info.
The REM50Z (Remote Equipment Monitor) Quad Channel Remote Temperature Sensor is a wall mountable Z-Wave remote temperature sensor for use with all Z-Wave systems.This sensor is ideal for remotely monitoring up to 4 operating temperatures on HVAC systems: Supply, Return, and Refrigeration In/Out Line Temps.Additionally, the REM50 has a single channel contact closure / voltage detection circuit that can be used to monitor and report Condensate Pan fill level of the HVAC system.Features Z-Wave 500 Series RadioSupports Z-Wave PlusQuad Temp Sensor Circuits:+/- 1 degree F, Range:-40F to 120FoDesigned for 10k Thermistor temp sensors, not included1 Contact Closure / Voltage Detection CircuitoDesigned to detect Float Switch closure, not included6 Status LEDsDesigned for interior use in mechanical room, attic or crawlspaceCompatible with RCS Z-Wave ThermostatsCompatible with all Z-Wave systemsWall MountableSmall, Thin, LightweightGrey, PaintableDimensions5.10 X 2.25 X 0.9Power1628 VAC1224 VDC
Please read the user manual before installing the product.
In order to include (add) a Z-Wave device to a network it must be in factory default state. Please make sure to reset the device into factory default. You can do this by performing an Exclusion operation as described below in the manual. Every Z-Wave controller is able to perform this operation however it is recommended to use the primary controller of the previous network to make sure the very device is excluded properly from this network.
This device also allows to be reset without any involvement of a Z-Wave controller. This procedure should only be used when the primary controller is inoperable.
Factory ResetNOTE: A Factory Reset should only be performed if the network controller is missing or inoperable.To reset the REM50Zs configurations and Z-Wave parameters to Factory Settings (Including association groups and scene configurations), and remove the REM50Z from any Z-Wave network:1. Hold down the Install button for approximately 10 seconds2. Release the install button (the REM50Z will reset all internal configuration including Z-Wave configurations). The unit will then reset.3. When the Status LED begins to blink (un-enrolled) the unit has finished restoring configurations is running in normal mode.A Restore Defaults will be performed automatically when removed from a network.
ATTENTION: only authorized technicians under consideration of the country-specific installation guidelines/norms may do works with mains power. Prior to the assembly of the product, the voltage network has to be switched off and ensured against re-switching.
On factory default the device does not belong to any Z-Wave network. The device needs to be added to an existing wireless network to communicate with the devices of this network. This process is called Inclusion.
Devices can also be removed from a network. This process is called Exclusion. Both processes are initiated by the primary controller of the Z-Wave network. This controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is then performed doing a special manual action right on the device.
Here are a few hints for network installation if things dont work as expected.
Z-Wave devices control other Z-Wave devices. The relationship between one device controlling another device is called association. In order to control a different device, the controlling device needs to maintain a list of devices that will receive controlling commands. These lists are called association groups and they are always related to certain events (e.g. button pressed, sensor triggers, ...). In case the event happens all devices stored in the respective association group will receive the same wireless command wireless command, typically a 'Basic Set' Command.
Group Number | Maximum Nodes | Description |
---|---|---|
1 | 1 | Z-Wave Plus Lifeline -Device Reset LocallySupply Air Sensor (Multilevel Sensor Report and Multilevel Sensor Report, Multichannel)Return Air Sensor (Multilevel Sensor Report, Multichannel)Coil Low Sensor (Multilevel Sensor Report, Multichannel)Coil High Sensor (Multilevel Sensor Report, Multichannel)Float Sensor(Notification Report) |
2 | 2 | Supply Air Sensor (Multilevel Sensor Report, Multichannel) |
3 | 2 | Return Air Sensor (Multilevel Sensor Report, Multichannel) |
4 | 2 | Temp - S3 Sensor (Multilevel Sensor Report, Multichannel) |
5 | 2 | Temp - S4 Sensor (Multilevel Sensor Report, Multichannel) |
6 | 2 | Float SW(Notification Report) |
Hardware Platform | ZM5202 |
Device Type | Notification Sensor |
Network Operation | Always On Slave |
Firmware Version | HW: 1 FW: 6.61:01.00 |
Z-Wave Version | 6.61.00 |
Certification ID | ZC10-18076173 |
Z-Wave Product Id | 0x0010.0x454D.0x3530 |
Color | Gray |
Sensors | Air TemperatureVoltage |
Firmware Updatable | Updatable by Consumer by RF |
Supported Notification Types | Water Alarm |
Frequency | XXfrequency |
Maximum transmission power | XXantenna |