Z-Wave is the international wireless protocol for communication in the Smart Home. This device is suited for use in the region mentioned in the Quickstart section.
Z-Wave ensures a reliable communication by reconfirming every message (two-way communication) and every mains powered node can act as a repeater for other nodes (meshed network) in case the receiver is not in direct wireless range of the transmitter.
This device and every other certified Z-Wave device can be used together with any other certified Z-Wave device regardless of brand and origin as long as both are suited for the same frequency range.
If a device supports secure communication it will communicate with other devices secure as long as this device provides the same or a higher level of security. Otherwise it will automatically turn into a lower level of security to maintain backward compatibility.
For more information about Z-Wave technology, devices, white papers etc. please refer to www.z-wave.info.
The module is mounted via a bracket, it is tamper protected and has a back-up battery.Three Inputs for the connection of: Analogue sensors with voltage 0~12VDigital sensors with voltage 0~12VPotential-free outputs NC/NOOpen Collector Outputs OCThree Outputs for connecting actuators with a maximum of 24VDCSPDT (Single Pole, Double Throw) relay (toggle switch)functions:Configurable timer that automatically switches off after a preset period of time (default is 500 ms)The output can be set to activate automatically when the input terminals (see configuration setting)
Please read the user manual before installing the product.
In order to include (add) a Z-Wave device to a network it must be in factory default state. Please make sure to reset the device into factory default. You can do this by performing an Exclusion operation as described below in the manual. Every Z-Wave controller is able to perform this operation however it is recommended to use the primary controller of the previous network to make sure the very device is excluded properly from this network.
On factory default the device does not belong to any Z-Wave network. The device needs to be added to an existing wireless network to communicate with the devices of this network. This process is called Inclusion.
Devices can also be removed from a network. This process is called Exclusion. Both processes are initiated by the primary controller of the Z-Wave network. This controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is then performed doing a special manual action right on the device.
Here are a few hints for network installation if things dont work as expected.
Z-Wave devices control other Z-Wave devices. The relationship between one device controlling another device is called association. In order to control a different device, the controlling device needs to maintain a list of devices that will receive controlling commands. These lists are called association groups and they are always related to certain events (e.g. button pressed, sensor triggers, ...). In case the event happens all devices stored in the respective association group will receive the same wireless command wireless command, typically a 'Basic Set' Command.
Group Number | Maximum Nodes | Description |
---|---|---|
1 | 5 | The Lifeline Association is automatically established between the Z-Wave controller and the device at inclusion and defines what information is exchanged between the Z-Wave controller and the device. |
2 | 5 | When a signal input is triggered, the unit first sends a BASIC Set ON. When the preset timer expires, it sends a BASIC Set OFF. |
3 | 5 | When a signal input is triggered, the unit first sends a BASIC Set ON. When the preset timer expires, it sends a BASIC Set OFF. |
4 | 5 | When a signal input is triggered, the unit first sends a BASIC Set ON. When the preset timer expires, it sends a BASIC Set OFF. |
Z-Wave products are supposed to work out of the box after inclusion, however certain configuration can adapt the function better to user needs or unlock further enhanced features.
IMPORTANT: Controllers may only allow configuring signed values. In order to set values in the range 128 ... 255 the value sent in the application shall be the desired value minus 256. For example: To set a parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56. In case of a two byte value the same logic applies: Values greater than 32768 may needed to be given as negative values too.
Several settings of the signal input and its triggering behaviour. Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 | No Relay is triggered, No Voltage is present, triggers below lowthreshold |
2 - 0 | Relay 1 is triggered, No Voltage is present, triggers below lowthreshold |
4 - 0 | Relay 2 is triggered, No Voltage is present, triggers below lowthreshold |
6 - 0 | Relay 1 and 2 are triggered, No Voltage is present, triggers below lowthreshold |
8 - 0 | Relay 3 is triggered, No Voltage is present, triggers below lowthreshold |
10 - 0 | Relay 1 and 3 are triggered, No Voltage is present, triggers below lowthreshold |
14 - 0 | Relay 1, 2 and 3 are triggered, No Voltage is present, triggers below lowthreshold |
64 - 0 | No Relay is triggered, 3,3V is present, triggers below lowthreshold |
66 - 0 | Relay 1 is triggered, 3,3V is present, triggers below lowthreshold |
68 - 0 | Relay 2 is triggered, 3,3V is present, triggers below lowthreshold |
70 - 0 | Relay 1 and 2 are triggered, 3,3V is present, triggers below lowthreshold |
72 - 0 | Relay 3 is triggered, 3,3V is present, triggers below lowthreshold |
74 - 0 | Relay 1 and 3 are triggered, 3,3V is present, triggers below lowthreshold |
78 - 0 | Relay 1, 2 and 3 are triggered, 3,3V is present, triggers below lowthreshold |
128 - 0 | No Relay is triggered, No Voltage is present, triggers above highthreshold |
130 - 0 | Relay 1 is triggered, No Voltage is present, triggers above highthreshold |
132 - 0 | Relay 2 is triggered, No Voltage is present, triggers above highthreshold |
134 - 0 | Relay 1 and 2 are triggered, No Voltage is present, triggers above highthreshold |
136 - 0 | Relay 3 is triggered, No Voltage is present, triggers above highthreshold |
138 - 0 | Relay 1 and 3 are triggered, No Voltage is present, triggers above highthreshold |
142 - 0 | Relay 1, 2 and 3 are triggered, No Voltage is present, triggers above highthreshold |
192 - 0 | No Relay is triggered, 3,3V is present, triggers above highthreshold |
194 - 0 | Relay 1 is triggered, 3,3V is present, triggers above highthreshold |
196 - 0 | Relay 2 is triggered, 3,3V is present, triggers above highthreshold |
198 - 0 | Relay 1 and 2 are triggered, 3,3V is present, triggers above highthreshold |
200 - 0 | Relay 3 is triggered, 3,3V is present, triggers above highthreshold |
202 - 0 | Relay 1 and 3 are triggered, 3,3V is present, triggers above highthreshold |
206 - 0 | Relay 1, 2 and 3 are triggered, 3,3V is present, triggers above highthreshold |
12 - 0 | Relay 2 and 3 are triggered, No Voltage is present, triggers below lowthreshold |
76 - 0 | Relay 2 and 3 are triggered, 3,3V is present, triggers below lowthreshold |
140 - 0 | Relay 2 and 3 are triggered, No Voltage is present, triggers above highthreshold |
204 - 0 | Relay 2 and 3 are triggered, 3,3V is present, triggers above highthreshold |
Setting of the voltage drop below which the signal input is triggered Size: 1 Byte, Default Value: 10
Setting | Description |
---|---|
0 - 255 | Adjustable from 0 - 255 in 100mV steps (10 = 1000mV = 1.0V) |
Same as Parameter 1, but applies to Signal Input 3 Size: 1 Byte, Default Value: 64
Setting | Description |
---|---|
0 | No Relay is triggered, No Voltage is present, triggers below lowthreshold |
2 - 0 | Relay 1 is triggered, No Voltage is present, triggers below lowthreshold |
4 - 0 | Relay 2 is triggered, No Voltage is present, triggers below lowthreshold |
6 - 0 | Relay 1 and 2 are triggered, No Voltage is present, triggers below lowthreshold |
8 - 0 | Relay 3 is triggered, No Voltage is present, triggers below lowthreshold |
10 - 0 | Relay 1 and 3 are triggered, No Voltage is present, triggers below lowthreshold |
12 - 0 | Relay 2 and 3 are triggered, No Voltage is present, triggers below lowthreshold |
14 - 0 | Relay 1, 2 and 3 are triggered, No Voltage is present, triggers below lowthreshold |
64 - 0 | No Relay is triggered, 3,3V is present, triggers below lowthreshold |
66 - 0 | Relay 1 is triggered, 3,3V is present, triggers below lowthreshold |
68 - 0 | Relay 2 is triggered, 3,3V is present, triggers below lowthreshold |
70 - 0 | Relay 1 and 2 are triggered, 3,3V is present, triggers below lowthreshold |
72 - 0 | Relay 3 is triggered, 3,3V is present, triggers below lowthreshold |
74 - 0 | Relay 1 and 3 are triggered, 3,3V is present, triggers below lowthreshold |
76 - 0 | Relay 2 and 3 are triggered, 3,3V is present, triggers below lowthreshold |
78 - 0 | Relay 1, 2 and 3 are triggered, 3,3V is present, triggers below lowthreshold |
128 - 0 | No Relay is triggered, No Voltage is present, triggers above highthreshold |
130 - 0 | Relay 1 is triggered, No Voltage is present, triggers above highthreshold |
132 - 0 | Relay 2 is triggered, No Voltage is present, triggers above highthreshold |
134 - 0 | Relay 1 and 2 are triggered, No Voltage is present, triggers above highthreshold |
136 - 0 | Relay 3 is triggered, No Voltage is present, triggers above highthreshold |
138 - 0 | Relay 1 and 3 are triggered, No Voltage is present, triggers above highthreshold |
140 - 0 | Relay 2 and 3 are triggered, No Voltage is present, triggers above highthreshold |
142 - 0 | Relay 1, 2 and 3 are triggered, No Voltage is present, triggers above highthreshold |
192 - 0 | No Relay is triggered, 3,3V is present, triggers above highthreshold |
194 - 0 | Relay 1 is triggered, 3,3V is present, triggers above highthreshold |
196 - 0 | Relay 2 is triggered, 3,3V is present, triggers above highthreshold |
198 - 0 | Relay 1 and 2 are triggered, 3,3V is present, triggers above highthreshold |
200 - 0 | Relay 3 is triggered, 3,3V is present, triggers above highthreshold |
202 - 0 | Relay 1 and 3 are triggered, 3,3V is present, triggers above highthreshold |
204 - 0 | Relay 2 and 3 are triggered, 3,3V is present, triggers above highthreshold |
206 - 0 | Relay 1, 2 and 3 are triggered, 3,3V is present, triggers above highthreshold |
Setting for the duration of the switching time when the relay output is switched. Size: 1 Byte, Default Value: 5
Setting | Description |
---|---|
0 | relay output is permanently switched |
1 - 255 | Adjustable duration from 1 - 255 in 100ms steps |
Setting for the duration of the switching time at association group 4 when signal input is triggered. Size: 1 Byte, Default Value: 180
Setting | Description |
---|---|
0 | Switched permanently |
1 - 255 | Adjustable duration from 1 - 255 in seconds |
Setting, from which voltage rise the signal input is triggered Size: 1 Byte, Default Value: 25
Setting | Description |
---|---|
0 - 255 | Adjustable from 0 - 255 in 100mV steps (25 = 2500mV = 2.5V) |
Setting of the voltage drop below which the signal input is triggered Size: 1 Byte, Default Value: 10
Setting | Description |
---|---|
0 - 255 | Adjustable from 0 - 255 in 100mV steps (10 = 1000mV = 1.0V) |
The interval time of the voltage report for signal input 1-3 Size: 1 Byte, Default Value: 30
Setting | Description |
---|---|
1 - 255 | Adjustable from 1 - 255 in minutes |
Setting whether a relay output must be switched in case of a sabotage alarm. Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 | No Relays are triggered |
2 - 0 | Relay 1 is triggered |
4 - 0 | Relay 2 is triggered |
6 - 0 | Relay 1 and 2 are triggered |
8 - 0 | Relay 3 is triggered |
10 - 0 | Relay 1 and 3 are triggered |
12 - 0 | Relay 2 and 3 are triggered |
14 - 0 | Relay 1, 2 and 3 are triggered |
Setting whether a signal input should send an armed and an unarmed message instead of a trigger signal. Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 | 0 = No signal input sends arm/disarm message |
1 | 1 = Signal input 1 sends arm/disarm message |
2 | 2 = Signal input 2 sends arm/disarm message |
3 | 3 = Signal input 3 sends arm/disarm message |
Setting for the duration of the switching time when the relay output is switched. Size: 1 Byte, Default Value: 5
Setting | Description |
---|---|
0 | relay output is permanently switched |
1 - 255 | Adjustable duration from 1 - 255 in 100ms steps |
Setting for the duration of the switching time at association group 2 when signal input is triggered. Size: 1 Byte, Default Value: 180
Setting | Description |
---|---|
0 | Switched permanently |
1 - 255 | Adjustable duration from 1 - 255 in seconds |
Setting, from which voltage rise the signal input is triggered Size: 1 Byte, Default Value: 25
Setting | Description |
---|---|
0 - 255 | Adjustable from 0 - 255 in 100mV steps (25 = 2500mV = 2.5V) |
Setting of the voltage drop below which the signal input is triggered Size: 1 Byte, Default Value: 10
Setting | Description |
---|---|
0 - 255 | Adjustable from 0 - 255 in 100mV steps (10 = 1000mV = 1.0V) |
Same as Parameter 1, but applies to Signal Input 2 Size: 1 Byte, Default Value: 64
Setting | Description |
---|---|
0 | No Relay is triggered, No Voltage is present, triggers below lowthreshold |
2 - 0 | Relay 1 is triggered, No Voltage is present, triggers below lowthreshold |
4 - 0 | Relay 2 is triggered, No Voltage is present, triggers below lowthreshold |
6 - 0 | Relay 1 and 2 are triggered, No Voltage is present, triggers below lowthreshold |
8 - 0 | Relay 3 is triggered, No Voltage is present, triggers below lowthreshold |
10 - 0 | Relay 1 and 3 are triggered, No Voltage is present, triggers below lowthreshold |
12 - 0 | Relay 2 and 3 are triggered, No Voltage is present, triggers below lowthreshold |
14 - 0 | Relay 1, 2 and 3 are triggered, No Voltage is present, triggers below lowthreshold |
64 - 0 | No Relay is triggered, 3,3V is present, triggers below lowthreshold |
66 - 0 | Relay 1 is triggered, 3,3V is present, triggers below lowthreshold |
68 - 0 | Relay 2 is triggered, 3,3V is present, triggers below lowthreshold |
70 - 0 | Relay 1 and 2 are triggered, 3,3V is present, triggers below lowthreshold |
72 - 0 | Relay 3 is triggered, 3,3V is present, triggers below lowthreshold |
74 - 0 | Relay 1 and 3 are triggered, 3,3V is present, triggers below lowthreshold |
76 - 0 | Relay 2 and 3 are triggered, 3,3V is present, triggers below lowthreshold |
78 - 0 | Relay 1, 2 and 3 are triggered, 3,3V is present, triggers below lowthreshold |
128 - 0 | No Relay is triggered, No Voltage is present, triggers above highthreshold |
130 - 0 | Relay 1 is triggered, No Voltage is present, triggers above highthreshold |
132 - 0 | Relay 2 is triggered, No Voltage is present, triggers above highthreshold |
134 - 0 | Relay 1 and 2 are triggered, No Voltage is present, triggers above highthreshold |
136 - 0 | Relay 3 is triggered, No Voltage is present, triggers above highthreshold |
138 - 0 | Relay 1 and 3 are triggered, No Voltage is present, triggers above highthreshold |
140 - 0 | Relay 2 and 3 are triggered, No Voltage is present, triggers above highthreshold |
142 - 0 | Relay 1, 2 and 3 are triggered, No Voltage is present, triggers above highthreshold |
192 - 0 | No Relay is triggered, 3,3V is present, triggers above highthreshold |
194 - 0 | Relay 1 is triggered, 3,3V is present, triggers above highthreshold |
196 - 0 | Relay 2 is triggered, 3,3V is present, triggers above highthreshold |
198 - 0 | Relay 1 and 2 are triggered, 3,3V is present, triggers above highthreshold |
200 - 0 | Relay 3 is triggered, 3,3V is present, triggers above highthreshold |
202 - 0 | Relay 1 and 3 are triggered, 3,3V is present, triggers above highthreshold |
204 - 0 | Relay 2 and 3 are triggered, 3,3V is present, triggers above highthreshold |
206 - 0 | Relay 1, 2 and 3 are triggered, 3,3V is present, triggers above highthreshold |
Setting for the duration of the switching time when the relay output is switched. Size: 1 Byte, Default Value: 5
Setting | Description |
---|---|
0 | relay output is permanently switched |
1 - 255 | Adjustable duration from 1 - 255 in 100ms steps |
Setting for the duration of the switching time at association group 3 when signal input is triggered. Size: 1 Byte, Default Value: 180
Setting | Description |
---|---|
0 | Switched permanently |
1 - 255 | Adjustable duration from 1 - 255 in seconds |
Setting, from which voltage rise the signal input is triggered Size: 1 Byte, Default Value: 25
Setting | Description |
---|---|
0 - 255 | Adjustable from 0 - 255 in 100mV steps (25 = 2500mV = 2.5V) |
Hardware Platform | SD3502 |
Device Type | Notification Sensor |
Network Operation | Always On Slave |
Firmware Version | HW: 1 FW: 1.00:00.04 |
Z-Wave Version | 6.81.06 |
Certification ID | ZC10-20076949 |
Z-Wave Product Id | 0x0403.0x0003.0x0007 |
Security V2 | S2_UNAUTHENTICATED ,S2_AUTHENTICATED |
Frequency | XXfrequency |
Maximum transmission power | XXantenna |